Inspections for the day of: Friday, December 1, 1995.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorLee Rice
TitlePLM-CHIEF INSPECTOR
Phone #794-9486
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM95-01713 INSP - Plumbing Rough-in12/1/199512/1/199512/1/1995 12:00:00 AMPFAIL
gave correction notice to forman on the job, Hank Reader. Corections: 1. Repipe (4) floor drains with individual vents up through floor. (They were tied together below floor) and 2. replace 2" waste with 3" where fixture units exceed 8 FU's. this is on the line going to the grease trap. Commercial floor sinks are 3 FU'S.
PLM95-01844 INSP - Plumbing Rough-in12/1/199512/1/199512/1/1995 12:00:00 AMPPASS
4 W/C 4 BASIN 4 TUB 2 SINK 2 W/B 2 W/H AND ONE HAS A BAR SINK NOT SURE WHICH ONE SORRY DUPLEX: r/i ok, Lee
PLM95-01849 INSP - Plumbing Rough-in12/1/199512/1/199512/1/1995 12:00:00 AMPPASS
9TH FLOOR UNIT 902 LATE PM SAME FIXTURES FOR SUITE 903 : waste and vent r/i and test ok
PLM4041708 INSP - Plumbing Rough-in12/1/199512/1/199512/19/1905 12:00:00 AMPPART
CORE ROOF DRAIN 5-8-not witnessed, will call back in FLOOR 5-10 WASTE AND VENTS-ok partial, one test(waste and vent)ok