Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04102 Electrical Rough-In12/1/200512/1/200512/1/2005 4:48:19 PMPPASS
ceiling insp///steve; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa met with contr to fix low volt cables in clg. ok to cover clg
ELE05-04290 Electrical Rough-In12/1/200512/1/200512/1/2005 3:42:51 PMPFAIL
robert --call 1st before insp for access; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, left corr notice, 358.30 emt shall be securely fastened within 3' of panel,330.17 mc cable shall be protected in accordance with 300.4(A)&(D) where installed through or parallel to framing members,300.4 mc cable subject to physical damage shall be protected, i.e. cable shall not be run inside valley of 2x4 studs, 110.26(F)(1)(b) there shall be no foreign piping above dedicated space unless protection is provided.
ELE05-01814 Permanent Service12/1/200512/1/200512/1/2005 1:21:23 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook called contr to show label on main that gear is suitable for service entrance. He will open up and call
ELE05-04323 Final12/1/200512/1/200512/1/2005 12:38:20 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook see ri
ELE05-04312 Electrical Rough-In11/30/200512/1/200512/1/2005 10:27:04 AMAPASS
natt-###-#### Note: please call 1/2 hr prior to inspection talked with contr, 2 plcs 1 1/4", rest ok to cover, 2 new ckts from panel to verify at final
ELE05-03778 Final11/30/200512/1/200512/1/2005 9:46:54 AMAPASS
Scheduled by a contractor via Hello! on 11/30/2005 at 11:42:11 AM. Contact: ###-####. 0k to final
ELE05-01814 Permanent Service11/30/200512/1/200512/1/2005 8:47:43 AMANR
jeremy Note: panel; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, said to label house panel, provide clearance for house panel and call back in.
ELE05-04323 Electrical Rough-In12/1/200512/1/200512/1/2005 12:00:00 AMPPART
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook walls only ok to cover, called contr to strap 1 set mc cable from box and a couple 1 1/4" areas. Panel not set, will recall to inspect ltr.