FIR05-00700
| INSP-Sprinkler Rough-in/Hydro | 11/30/2005 | 12/1/2005 | 12/2/2005 9:27:13 AM | A | PART |
|
|
Overhead rough-in is good for cover, check possible obstruction formed by a column, see approved plans for location.
|
FIR05-00778
| INSP-Final Inspection | 12/1/2005 | 12/1/2005 | 12/2/2005 8:47:38 AM | P | FAIL |
|
|
Missing coverage at stair landing 1st level, ssu under stairs is partially blocked, need ceiling and canopies installed at two areas, the remainder of rough-in for this permit is okay.
|
BLD05-02147
| FIRE-Final Inspection | 12/1/2005 | 12/1/2005 | 12/1/2005 3:52:22 PM | P | PASS |
|
|
Fire life safety passed, the sliding door kickplates at the potting room that prevented emergency breakaway operation were removed while on site.
|
FIR05-00385
| INSP-Sprinkler Rough-in | 11/30/2005 | 12/1/2005 | 12/1/2005 3:02:26 PM | P | CANC |
|
|
Inspection to be rescheduled per agreement with Mike at ###-#### for 12/2 am.
|
BLD05-01926
| FIRE-Final Inspection | 11/30/2005 | 12/1/2005 | 12/1/2005 2:55:10 PM | A | PASS |
|
|
Fire life safety requirements have been met, inspection passed.
|
BLD05-01926
| FIRE-Alarm Testing | 11/30/2005 | 12/1/2005 | 12/1/2005 2:53:59 PM | A | DONE |
|
|
Duplicate inspection already called in.
|
BLD05-02852
| FIRE-Final Inspection | 11/30/2005 | 12/1/2005 | 12/1/2005 2:52:32 PM | A | PART |
|
|
hilary - ###-#### A letter has been provided regarding the density available for the racking installation.
|
BLD05-01927
| FIRE-Final Inspection | 11/30/2005 | 12/1/2005 | 12/1/2005 2:39:40 PM | A | PASS |
|
|
Fire life safety passed inspection.
|
BLD05-01927
| FIRE-Alarm Testing | 11/30/2005 | 12/1/2005 | 12/1/2005 2:36:23 PM | A | DONE |
|
|
Duplicate inspection already called in.
|
BLD05-02426
| FIRE-Final Inspection | 11/30/2005 | 12/1/2005 | 12/1/2005 1:54:32 PM | A | PART |
|
|
Life safety issues are acceptable pending fire alarm upgrade now required for the entire building.
|
MIS05-00199
| FIR-Final | 12/1/2005 | 12/1/2005 | 12/1/2005 1:07:37 PM | P | PASS |
|
|
c/n items are complete, life safety passed.
|
BLD05-01696
| FIRE-Final Inspection | 11/30/2005 | 12/1/2005 | 12/1/2005 12:47:59 PM | A | FAIL |
|
|
Provide fire extinguisher per note #22 on plan review, provide approved hardware at back restroom door per note #25, the main entry doors must meet req. of note # 27, provide verification of a current annual inspection on the existing fire sprinkler system.
|
BLD05-01209
| FIRE-Alarm Testing | 11/30/2005 | 12/1/2005 | 12/1/2005 12:41:59 PM | A | PART |
|
|
Verified sprinkler system monitoring per Sam Rogers instructions to enable store merchandising pre permit finals.
|
FIR05-00648
| INSP-Sprinkler Rough-in/Hydro | 11/30/2005 | 12/1/2005 | 12/1/2005 12:39:21 PM | P | FAIL |
|
|
Provide approved EQ attatchment methods for TJI's, upright coverage is blocked at area adjacent to restrooms by ductwork, sheetrock has been installed to full height where not shown, drop ceilings are not complete. The overhead hydro test passed inspection.
|
FIR05-00609
| INSP-Final Inspection | 11/30/2005 | 12/1/2005 | 12/1/2005 9:43:37 AM | A | PART |
|
|
Fire alarm for this permit is acceptable, corrections have been completed, final pending shell alarm finals wip.
|
BLD04-02676
| FIRE-Final Inspection | 11/30/2005 | 12/1/2005 | 12/1/2005 9:22:27 AM | A | DONE |
|
|
This inspection has already been completed and passed the previous day, 11/30.
|
BLD05-01916
| FIRE-Final Inspection | 11/30/2005 | 12/1/2005 | 12/1/2005 9:20:06 AM | A | PASS |
|
|
Fire life safety is satisfactory.
|
FIR05-00535
| INSP-Final Inspection | 11/30/2005 | 12/1/2005 | 12/1/2005 9:17:20 AM | A | PASS |
|
|
Fire alarm passed inspection, two incorrectly cd rated devices were replaced with the correct device while on site.
|
FIR05-00603
| INSP-Final Inspection | 12/1/2005 | 12/1/2005 | 12/1/2005 12:00:00 AM | A | PASS |
|
|
Fire sprinkler passed final inspection.
|
FIR05-00643
| INSP-Final Inspection | 12/1/2005 | 12/1/2005 | 12/1/2005 12:00:00 AM | A | PASS |
|
|
The hood suppression system operated correctly under test conditions.
|
FIR05-00625
| INSP-Final Inspection | 12/1/2005 | 12/1/2005 | 12/1/2005 12:00:00 AM | P | PASS |
|
|
Fire alarm finaled.
|
FIR05-00617
| INSP-Final Inspection | 12/1/2005 | 12/1/2005 | 12/1/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinkler passed inspection, missing 401 2nd pc. canopy to be installed today per contractor.
|