Inspections for the day of: Thursday, December 1, 2005.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00700 INSP-Sprinkler Rough-in/Hydro11/30/200512/1/200512/2/2005 9:27:13 AMAPART
Overhead rough-in is good for cover, check possible obstruction formed by a column, see approved plans for location.
FIR05-00778 INSP-Final Inspection12/1/200512/1/200512/2/2005 8:47:38 AMPFAIL
Missing coverage at stair landing 1st level, ssu under stairs is partially blocked, need ceiling and canopies installed at two areas, the remainder of rough-in for this permit is okay.
BLD05-02147 FIRE-Final Inspection12/1/200512/1/200512/1/2005 3:52:22 PMPPASS
Fire life safety passed, the sliding door kickplates at the potting room that prevented emergency breakaway operation were removed while on site.
FIR05-00385 INSP-Sprinkler Rough-in11/30/200512/1/200512/1/2005 3:02:26 PMPCANC
Inspection to be rescheduled per agreement with Mike at ###-#### for 12/2 am.
BLD05-01926 FIRE-Final Inspection11/30/200512/1/200512/1/2005 2:55:10 PMAPASS
Fire life safety requirements have been met, inspection passed.
BLD05-01926 FIRE-Alarm Testing11/30/200512/1/200512/1/2005 2:53:59 PMADONE
Duplicate inspection already called in.
BLD05-02852 FIRE-Final Inspection11/30/200512/1/200512/1/2005 2:52:32 PMAPART
hilary - ###-#### A letter has been provided regarding the density available for the racking installation.
BLD05-01927 FIRE-Final Inspection11/30/200512/1/200512/1/2005 2:39:40 PMAPASS
Fire life safety passed inspection.
BLD05-01927 FIRE-Alarm Testing11/30/200512/1/200512/1/2005 2:36:23 PMADONE
Duplicate inspection already called in.
BLD05-02426 FIRE-Final Inspection11/30/200512/1/200512/1/2005 1:54:32 PMAPART
Life safety issues are acceptable pending fire alarm upgrade now required for the entire building.
MIS05-00199 FIR-Final12/1/200512/1/200512/1/2005 1:07:37 PMPPASS
c/n items are complete, life safety passed.
BLD05-01696 FIRE-Final Inspection11/30/200512/1/200512/1/2005 12:47:59 PMAFAIL
Provide fire extinguisher per note #22 on plan review, provide approved hardware at back restroom door per note #25, the main entry doors must meet req. of note # 27, provide verification of a current annual inspection on the existing fire sprinkler system.
BLD05-01209 FIRE-Alarm Testing11/30/200512/1/200512/1/2005 12:41:59 PMAPART
Verified sprinkler system monitoring per Sam Rogers instructions to enable store merchandising pre permit finals.
FIR05-00648 INSP-Sprinkler Rough-in/Hydro11/30/200512/1/200512/1/2005 12:39:21 PMPFAIL
Provide approved EQ attatchment methods for TJI's, upright coverage is blocked at area adjacent to restrooms by ductwork, sheetrock has been installed to full height where not shown, drop ceilings are not complete. The overhead hydro test passed inspection.
FIR05-00609 INSP-Final Inspection11/30/200512/1/200512/1/2005 9:43:37 AMAPART
Fire alarm for this permit is acceptable, corrections have been completed, final pending shell alarm finals wip.
BLD04-02676 FIRE-Final Inspection11/30/200512/1/200512/1/2005 9:22:27 AMADONE
This inspection has already been completed and passed the previous day, 11/30.
BLD05-01916 FIRE-Final Inspection11/30/200512/1/200512/1/2005 9:20:06 AMAPASS
Fire life safety is satisfactory.
FIR05-00535 INSP-Final Inspection11/30/200512/1/200512/1/2005 9:17:20 AMAPASS
Fire alarm passed inspection, two incorrectly cd rated devices were replaced with the correct device while on site.
FIR05-00603 INSP-Final Inspection12/1/200512/1/200512/1/2005 12:00:00 AMAPASS
Fire sprinkler passed final inspection.
FIR05-00643 INSP-Final Inspection12/1/200512/1/200512/1/2005 12:00:00 AMAPASS
The hood suppression system operated correctly under test conditions.
FIR05-00625 INSP-Final Inspection12/1/200512/1/200512/1/2005 12:00:00 AMPPASS
Fire alarm finaled.
FIR05-00617 INSP-Final Inspection12/1/200512/1/200512/1/2005 12:00:00 AMPPASS
Fire sprinkler passed inspection, missing 401 2nd pc. canopy to be installed today per contractor.