ELE06-03928
| Electrical Rough-In | 12/1/2006 | 12/1/2006 | 12/1/2006 4:18:50 PM | P | CANC |
|
|
kevin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles contr called and asked to cancel and recall for next week
|
ELE06-04278
| Rough-In Permanent Service | 12/1/2006 | 12/1/2006 | 12/1/2006 4:02:24 PM | P | NH |
|
|
WE HAVE RELOCATED THE PANEL AND METER PER CUSTOMERS REQUEST AND ARE READY FOR INSPECTION. LOCK BOX ON TEMP.POLE OUT BACK AND THE CODE IS 1290.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called contr, locked out of site, they will recall
|
ELE06-04444
| Electrical Rough-In | 12/1/2006 | 12/1/2006 | 12/1/2006 3:46:57 PM | P | CANC |
|
|
john ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith wrong type insp, see rip
|
ELE06-04444
| Rough-In Permanent Service | 12/1/2006 | 12/1/2006 | 12/1/2006 3:44:44 PM | P | PASS |
|
|
john ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ric ok, p/s o/h rec ok
|
ELE06-03320
| Final | 12/1/2006 | 12/1/2006 | 12/1/2006 3:23:26 PM | P | PASS |
|
|
clyde ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
|
ELE06-04418
| Electrical Rough-In | 11/29/2006 | 12/1/2006 | 12/1/2006 2:58:24 PM | A | PASS |
|
|
Extended an existing garage receptacle circuit to a new motion detector light in the garage.Aslo ran 2 new 1 20 volt afci circuit to bld quad plex Thanks!!! (6111167s)Tech/Dan/ ###-####.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final
|
ELE06-04451
| Permanent Service | 12/1/2006 | 12/1/2006 | 12/1/2006 2:50:44 PM | P | PASS |
|
|
Mike ###-#### p/s o/h n (rec) ok
|
ELE06-04450
| Rough-In Permanent Service | 12/1/2006 | 12/1/2006 | 12/1/2006 2:15:59 PM | P | FAIL |
|
|
mark ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, no answer, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 300.4(1) edge of bored holes shall be 1 1/4" from edge of framing members, 250.24(A)(4) grounding connection shall not be made to grounded conductor on load side of service disc
|
ELE06-04312
| Electrical Rough-In | 12/1/2006 | 12/1/2006 | 12/1/2006 1:06:03 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 12/1/2006 at 9:10:32 AM. Contact: ###-####. ric ok
|
ELE06-04235
| Electrical Rough-In | 11/30/2006 | 12/1/2006 | 12/1/2006 10:48:12 AM | A | PART |
|
|
Contact: Francis Lee - Partial Final; Phone #: ###-#### Internet Inspection Request from: Deb McCoy lower plaza conf room switch ok for part final, will be starting more work on this permit
|
ELE06-04243
| Electrical Rough-In | 11/30/2006 | 12/1/2006 | 12/1/2006 10:25:14 AM | A | PASS |
|
|
mitch - please call for access and timing ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ric ok, check outlet spacing at final
|
ELE06-03721
| Final | 11/30/2006 | 12/1/2006 | 12/1/2006 10:07:23 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/30/2006 at 12:03:15 PM. Contact: ###-####. ok to final
|
ELE06-04432
| Permanent Service | 11/30/2006 | 12/1/2006 | 12/1/2006 9:17:34 AM | A | PASS |
|
|
WE ARE READY FOR A FINAL INSPECTION AT THIS LOCATION. IF YOU NEED ACCESS IN TO THE CABINET TO SEE THE WORK INSIDE, PLEASE CALL RYAN w/TRACK UTILITIES AT ###-#### TO GAIN ACCESS AND ARRANGE FOR HIM TO MEET OYU AT THE SITE.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called to verify address, actual address 4705 Wylie, by apartments, p/s u/g n ok
|
ELE06-04415
| Electrical Rough-In | 11/29/2006 | 12/1/2006 | 12/1/2006 9:10:53 AM | A | PASS |
|
|
Ready for rough-in, please contact George, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters walls only ok to cover
|
ELE06-04110
| Final | 11/30/2006 | 12/1/2006 | 12/1/2006 8:33:47 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton ok to final
|
ELE06-04110
| Final | 11/30/2006 | 12/1/2006 | 11/30/2006 4:12:54 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
|