ELE07-02961 ELE-Aging Inspection12/1/200912/1/200912/4/2009 9:28:20 AM DONE
no activity
ELE07-03466 ELE-Aging Inspection12/1/200912/1/200912/4/2009 9:27:52 AM DONE
no activity
ELE09-00692 Final12/1/200912/1/200912/1/2009 4:12:43 PMPPASS
Mark ###-####//please call 30 min prior ok to final, no esc this project
ESC09-00264 General Inspection12/1/200912/1/200912/1/2009 3:37:17 PMPPASS
looked ok
ESC09-00703 General Inspection12/1/200912/1/200912/1/2009 3:36:15 PMPPASS
looked ok
ESC09-00503 General Inspection12/1/200912/1/200912/1/2009 3:35:24 PMPPASS
looked ok, building fence
ESC09-00681 General Inspection12/1/200912/1/200912/1/2009 3:33:40 PMPPART
see 460 comments
ESC09-00510 General Inspection12/1/200912/1/200912/1/2009 3:32:03 PMPPART
see 460 comments
ELE09-02254 Electrical Rough-In12/1/200912/1/200912/1/2009 3:24:41 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Bryan Atkins ok to cover u/g anop
ELE09-02318 Temporary Service12/1/200912/1/200912/1/2009 2:27:38 PMPPASS
###-#### Richard called, left survey, NEC 312.5 all conductors entering enclosure shall have abrasion protection, 406.8(B) all 15 and 20A receptacles shall be a listed weather resistant type
ELE09-01923 Final11/30/200912/1/200912/1/2009 1:14:25 PMPPASS
kyle Phone #: ###-#### ok to final
ELE09-02306 Final11/30/200912/1/200912/1/2009 12:23:07 PMPCANC
Phone #: ###-#### Internet Inspection Request from: JESS BECK wrong type request, see conference, no esc this project
ELE09-02306 Conference12/1/200912/1/200912/1/2009 12:22:49 PMPDONE
Phone #: ###-#### Internet Inspection Request from: JESS BECK met contractor, reviewed overhead clearances, grounding, new service for structure, no esc this project
ELE09-01474 Final11/30/200912/1/200912/1/2009 11:38:49 AMPPASS
please call me so i can make sure the house is open. Thanks Dave ###-#### Phone #: ###-#### Internet Inspection Request from: jason shifflett called, left message, ok to final
ELE09-02314 Electrical Rough-In11/30/200912/1/200912/1/2009 10:38:08 AMANH
Phone #: ###-#### Internet Inspection Request from: Jenni Keller called, left card, told to re-schedule when available, fee due, no esc this project
ELE09-02311 Temporary Service11/30/200912/1/200912/1/2009 10:06:16 AMAPASS
Ed Phone #: ###-#### called, t/s u/g n ok
ELE09-02052 Electrical Rough-In11/30/200912/1/200912/1/2009 9:18:06 AMAPASS
Bruce-Underground-Please call at least 1 hour prior Phone #: ###-#### ok to cover u/g anop, no esc this project
ELE09-02307 Permanent Service11/30/200912/1/200912/1/2009 8:35:10 AMAFAIL
Gary Phone #: ###-#### called contractor, told to install ground rods and safe off sub-panel or install, will call for pm inspection, no esc this project
ELE09-02298 Permanent Service11/30/200912/1/200912/1/2009 8:09:45 AMAPASS
This is ready and as we spoke today the grond is encased Phone #: ###-#### Internet Inspection Request from: jason shifflett ok to backfill concrete encased electrode, p/s o/h rec ok