Inspections for the day of: Tuesday, December 1, 2009.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDoug A Poedy
TitleELE-INSPECTOR
Phone #447-7209
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-02321 Rough-In Permanent Service12/1/200912/1/200912/1/2009 3:11:32 PMPPASS
thanks! Phone #: ###-#### Internet Inspection Request from: Darryn Coburn. P/S U/G Connect ok. Ok to cover.
ELE09-02014 Final12/1/200912/1/200912/1/2009 2:50:59 PMPCANC
We would appreciate it if you could make this inspection a little later in the afternoon (we just need the ceiling for cover inspection today not a complete final)thank you Phone #: ###-#### Internet Inspection Request from: Brad Baker. Ceiling cover only.
ELE09-02014 Electrical Rough-In12/1/200912/1/200912/1/2009 2:50:35 PMPPASS
We would appreciate it if you could make this inspection a little later in the afternoon (we just need the ceiling for cover inspection today not a complete final)thank you Phone #: ###-#### Internet Inspection Request from: Brad Baker. Ok to cover ceiling.
ELE09-01928 Final12/1/200912/1/200912/1/2009 1:58:08 PMPPASS
Paul Phone #: ###-####. Ok final.
ELE09-01928 DOC - Permit Finaled12/1/200912/1/200912/1/2009 1:57:51 PMPPASS
ELE09-02287 Conference11/24/200912/1/200912/1/2009 12:42:31 PMPDONE
Ben ###-####
ELE09-02287 Electrical Rough-In12/1/200912/1/200912/1/2009 12:42:21 PMPPASS
Ben ###-####. Ok to cover shed and underground.
ELE09-01341 Final12/1/200912/1/200912/1/2009 12:13:25 PMPPASS
thanks! Phone #: ###-#### Internet Inspection Request from: Darryn Coburn. Ok final.
ELE09-01341 DOC - Permit Finaled12/1/200912/1/200912/1/2009 12:13:08 PMPPASS
ELE09-02320 Rough-In Permanent Service12/1/200912/1/200912/1/2009 11:55:13 AMPPASS
Thanks! Phone #: ###-#### Internet Inspection Request from: Darryn Coburn. P/S U/G connect ok. Ok to cover.
ESC09-00065 General Inspection12/1/200912/1/200912/1/2009 11:54:41 AMPPASS
ELE09-02267 Final12/1/200912/1/200912/1/2009 11:13:14 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Roy Kay. NEC 110.3 B Sq. D breakers in seimens panel. NEC 334.30. Securing and supporting. Staple Romex. NEC300.4 Protection of physical damage. Nail plates. NEC 408.4 Circuit directory needs to be filled out.
ELE09-02299 Rough-In Permanent Service11/30/200912/1/200912/1/2009 11:06:42 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe. P/S U/G connect ok.
ELE09-02301 Rough-In Permanent Service11/30/200912/1/200912/1/2009 11:05:59 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe. P/S U/G connect. Ok to cover.
ESC09-00321 General Inspection12/1/200912/1/200912/1/2009 10:37:43 AMAPASS
ESC09-00320 General Inspection12/1/200912/1/200912/1/2009 10:29:48 AMAPASS
ELE09-02313 Final11/30/200912/1/200912/1/2009 10:17:35 AMAPASS
Alan ###-####.Left survey NEC 210.8 A2 Garage door opener GFCI.