FIR09-00518
| INSP-Conference | 12/1/2009 | 12/1/2009 | 12/1/2009 3:02:48 PM | P | DONE |
|
|
Jerry MCAddams and I met with the builder and discussed the requirements for protection of the wet sprinkler system piping. He agreed to perform the work. We also discussed the lfie safety items related to th associated building permit including the fire alarm requirements..
|
BLD09-02053
| FIRE-Final Inspection | 12/1/2009 | 12/1/2009 | 12/1/2009 2:52:10 PM | P | PASS |
|
|
Life safety passed.
|
FIR09-00448
| INSP-Sprinkler Rough-in/Hydro | 12/1/2009 | 12/1/2009 | 12/1/2009 2:11:16 PM | P | PASS |
|
|
THe above ground hydro tests passed for both of the overhead systems.
|
FIR09-00419
| INSP-Sprinkler Rough-in/Hydro | 12/1/2009 | 12/1/2009 | 12/1/2009 1:29:00 PM | P | PASS |
|
|
Underground hydro test passed.
|
BLD09-02082
| FIRE-Final Inspection | 12/1/2009 | 12/1/2009 | 12/1/2009 1:26:54 PM | P | FAIL |
|
|
Fire sprinkler modifications are required due to sprinkler pendants located too close to one another. All other items appear to be ok.
|
BLD06-02723
| FIRE-Final Inspection | 11/30/2009 | 12/1/2009 | 12/1/2009 12:31:06 PM | A | PASS |
|
|
Life safety passed.
|
FIR09-00661
| INSP-Final Inspection | 11/30/2009 | 12/1/2009 | 12/1/2009 12:19:51 PM | A | FAIL |
|
|
Per the approved plans the maximum head spacing as hydraulically calculated is 112 sq. ft. As installed in the field the pendant heads are spaced up to 126 sq. ft. and in some locations the pendant even exceed 15'-0" apart.. I spoke with John at Commercial FIre and with Tim Frost in the office about this issue.
|
FIR09-00468
| INSP-Final Inspection | 11/30/2009 | 12/1/2009 | 12/1/2009 11:34:24 AM | A | PASS |
|
|
Permit finaled.
|
FIR09-00408
| INSP-Final Inspection | 11/30/2009 | 12/1/2009 | 12/1/2009 10:30:34 AM | A | PASS |
|
|
Permit finaled
|
FIR09-00672
| INSP-Final Inspection | 11/30/2009 | 12/1/2009 | 12/1/2009 7:20:15 AM | A | PASS |
|
|
Permit finaled
|