BLD11-00923
| FIRE-Final Inspection | 12/1/2011 | 12/1/2011 | 12/1/2011 3:14:57 PM | P | PART |
|
|
The lab area life safety is passed.
|
FIR11-00544
| INSP-Sprinkler Rough-in | 12/1/2011 | 12/1/2011 | 12/1/2011 2:20:37 PM | P | PASS |
|
|
The tenting is complete except for the top of the riser to main feed. This will be verified later. Piping can be covered.
|
FIR11-00559
| INSP-Final Inspection | 11/30/2011 | 12/1/2011 | 12/1/2011 2:19:33 PM | A | CANC |
|
|
Per phone discussion with Jake this inspeciton is being cancelled until the fire alarm system is functional.
|
BLD11-01119
| FIRE-Final Inspection | 12/1/2011 | 12/1/2011 | 12/1/2011 2:12:06 PM | P | PASS |
|
|
life safety passed
|
FIR11-00380
| INSP-Alarm Testing | 11/29/2011 | 12/1/2011 | 12/1/2011 9:45:45 AM | A | FAIL |
|
|
The strobes in the four patient rooms are overspaced. The two smoke detectors in the restrooms between the patient rooms are missing and will need to be installed or ok'd by plan review to remain deleted. The smoke detector at the double doors to the pedestrian walkway was left above the ceiling. The lone smoke detector that was left in the main corridor after the double doors were demo'd needs to be removed.
|