Inspections for the day of: Thursday, December 1, 2011.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-00923 FIRE-Final Inspection12/1/201112/1/201112/1/2011 3:14:57 PMPPART
The lab area life safety is passed.
FIR11-00544 INSP-Sprinkler Rough-in12/1/201112/1/201112/1/2011 2:20:37 PMPPASS
The tenting is complete except for the top of the riser to main feed. This will be verified later. Piping can be covered.
FIR11-00559 INSP-Final Inspection11/30/201112/1/201112/1/2011 2:19:33 PMACANC
Per phone discussion with Jake this inspeciton is being cancelled until the fire alarm system is functional.
BLD11-01119 FIRE-Final Inspection12/1/201112/1/201112/1/2011 2:12:06 PMPPASS
life safety passed
FIR11-00380 INSP-Alarm Testing11/29/201112/1/201112/1/2011 9:45:45 AMAFAIL
The strobes in the four patient rooms are overspaced. The two smoke detectors in the restrooms between the patient rooms are missing and will need to be installed or ok'd by plan review to remain deleted. The smoke detector at the double doors to the pedestrian walkway was left above the ceiling. The lone smoke detector that was left in the main corridor after the double doors were demo'd needs to be removed.