Inspections for the day of: Monday, December 1, 2014.
Number of inspections: 15
Percentage of inspections complete: 80 %
Percentage of inspections not complete: 20 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00735 INSP-Sprinkler Rough-in11/24/201411/25/2014 A 
RTC for Dry System, Bldg D 1st floor, please call Scott 30 minutes prior at ###-#### Phone #: ###-#### >> Inspection requested via web by Jacci Hunt
FIR14-00708 INSP-Sprinkler Rough-in11/26/201411/26/2014 P 
Matt Phone #: ###-####
FIR14-00531 INSP-Conference11/26/201411/26/2014 P 
Nate is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
FIR14-00735 INSP-Sprinkler Rough-in11/26/201412/1/201412/9/2014 3:09:32 PMPPART
FIR14-00460 INSP-Sprinkler Rough-in12/1/201412/1/201412/3/2014 7:29:13 AMPPART
Verified approved plans on site. Completed inspection for the first and second floor levels. Noted three areas in need of tenting adjustments, pendent head at the master bedroom closet needs relocated, three branchlines at the great room are not yet installed (no cover until inspected), minor field modifications at the first floor to branchline routing okayed, noted heads at the first floor office are not installed in the coffered ceiling members per plan- contractor to ensure obstruction criteria are met. Partial approval only. Basement level not yet finished for inspection.
BLD14-01034 FIRE-Final Inspection12/1/201412/1/201412/1/2014 3:30:22 PMPPASS
Life safety inspection passed.
FIR14-00828 INSP-Final Inspection12/1/201412/1/201412/1/2014 3:16:58 PMPCANC
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by Brian A Inspection cancelled via mobile web on Monday, December 01, 2014.
BLD14-02970 FIRE-Final Inspection12/1/201412/1/201412/1/2014 3:03:42 PMPPASS
Life safety passed provided "door to remain...." signage is posted at the main entry/exit.
FIR14-00787 INSP-Final Inspection12/1/201412/1/201412/1/2014 2:28:18 PMPPASS
New SD's and occupant notification related to the tenant remodel and per scope of work passed inspection and testing. Caps at SD during construction and non-functional door mags at the elevator lobby to be removed prior to BLD final/occupancy approval. Fire alarm permit finaled.
BLD14-02934 FIRE-Final Inspection12/1/201412/1/201412/1/2014 2:23:12 PMPPASS
Fire life safety inspection completed satisfactory. Missing doors and hardware at individual offices to be installed prior to structural final for verification at that time.
FIR14-00732 INSP-Final Inspection12/1/201412/1/201412/1/2014 2:21:05 PMPPASS
Fire sprinkler work passed final walkthrough. Permit finaled.
FIR14-00855 INSP-Final Inspection12/1/201412/1/201412/1/2014 2:19:54 PMPPASS
Fire alarm testing completed acceptable. Permit finaled.
FIR14-00844 INSP-Sprinkler Rough-in12/1/201412/1/201412/1/2014 11:53:50 AMPPART
Overhead work at the remodel areas okayed for ceiling cover. Coverage at the storage room adjusted while on site to meet OH spacing.
BLD14-03376 FIRE-Final Inspection12/1/201412/1/201412/1/2014 10:54:42 AMAPASS
Verified noted corrections. Fire life safety finaled.
FIR14-00662 INSP-Final Inspection11/26/201412/1/201412/1/2014 10:35:57 AMAPASS
Scope of fire sprinkler work completed and passed final inspection.