Inspections for the day of: Tuesday, December 1, 2015.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02370 ELE-Aging Inspection12/1/201512/1/201512/3/2015 11:38:22 AM CANC
too busy
ELE15-03627 Electrical Rough-In12/1/201512/1/201512/1/2015 3:47:51 PMPPASS
Jake is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates
New garage rough in ok cover
ELE15-01812 Electrical Rough-In11/30/201512/1/201512/1/2015 3:32:51 PMPPASS
Rough in inspection for POS/canopy. Phone #: ###-#### Inspection requested via web by William Salts
Point of service ceilings rough in ok cover
ELE15-03732 Rough-In Permanent Service12/1/201512/1/201512/1/2015 3:03:15 PMPFAIL
Please contact Gary ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson
* Unit 102 Living area wiring incomplete. Outlet jumper has been removed from box and pulled out of I-beams and hangs from ceiling.
334.10- NM cable shall not be exposed to damp or wet locations. Cover and drysheet entrance to unit 102.
Informed HVAC workers if they removed wiring with out letting electrical contractor know a stop work order would be issued
ELE15-03290 Final12/1/201512/1/201512/1/2015 1:53:24 PMPFAIL
Phone #: ###-#### Inspection requested via web by daniel bibikov
110.3- Receptacle outlets shall be wired to manufacturers instructions. Reverse polarity front bed.
314.25- All boxes shall have covers. Micro wave.
Front of house visqueened off correction on temp pole. called ldft message with contractor
Unlicensed individual working on job would not produce an electrical license or drivers license. Name given Tim Muzafarov driving Ultimate Electric vehicle license #
1/A 9M515. Ordered indivdual off job and he left.
ELE15-03117 Electrical Rough-In12/1/201512/1/201512/1/2015 12:54:16 PMPPASS
Ceiling Inspection, hard lid. Greg Milburn is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
2 conference rooms and IT room hardlids only rough in ok cover
ELE15-03853 Final11/30/201512/1/201512/1/2015 11:16:28 AMACANC
Phone #: ###-#### Inspection requested via web by Paula Gratiot Needed rough in inspection
ELE15-03853 Electrical Rough-In12/1/201512/1/201512/1/2015 11:16:11 AMPPASS
Phone #: ###-#### Inspection requested via web by Paula Gratiot House unoccupied at this time. Full house rewire rough in ok cover
ELE15-03827 Final11/30/201512/1/201512/1/2015 10:05:46 AMAPASS
Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan Final ok
ELE15-03847 Final11/30/201512/1/201512/1/2015 9:48:51 AMAPASS
Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan Final ok
ELE15-03847 Electrical Rough-In11/30/201512/1/201512/1/2015 9:39:58 AMAPASS
Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan Underground rough in ok cover
ELE15-03847 Permanent Service11/30/201512/1/201512/1/2015 9:31:22 AMAPASS
Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan p/s u/g rec ok
ELE15-03221 Final11/30/201512/1/201512/1/2015 8:47:06 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok