Inspections for the day of: Tuesday, December 1, 2015.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00586 INSP-Sprinkler Rough-in11/30/201512/1/201512/1/2015 2:47:26 PMPPASS
Rough-in passed. Riser not complete yet. Some of the uprights are too close to web members and will need adjusted to meet the three times rule. One branchline restraint added.
BLD15-04002 FIRE-Final Inspection12/1/201512/1/201512/1/2015 1:22:11 PMPPASS
life safety passed
BLD15-04156 FIRE-Final Inspection11/25/201512/1/201512/1/2015 12:13:57 PMPFAIL
Provide sticker at the main exit, provide annual inspection tag for the two fire extinguishers, provide revised floor plan to plan review showing the office in the back, provide missing canopies for the sprinkler heads.
BLD15-04227 FIRE-Final Inspection11/30/201512/1/201512/1/2015 10:11:35 AMACANC
Rescheduled for tomorrow per contact
FIR15-00832 INSP-Sprinkler Rough-in11/30/201512/1/201512/1/2015 8:56:46 AMAPASS
rough-in passed. piping can be covered