FIR15-00586
| INSP-Sprinkler Rough-in | 11/30/2015 | 12/1/2015 | 12/1/2015 2:47:26 PM | P | PASS |
|
|
Rough-in passed. Riser not complete yet. Some of the uprights are too close to web members and will need adjusted to meet the three times rule. One branchline restraint added.
|
BLD15-04002
| FIRE-Final Inspection | 12/1/2015 | 12/1/2015 | 12/1/2015 1:22:11 PM | P | PASS |
|
|
life safety passed
|
BLD15-04156
| FIRE-Final Inspection | 11/25/2015 | 12/1/2015 | 12/1/2015 12:13:57 PM | P | FAIL |
|
|
Provide sticker at the main exit, provide annual inspection tag for the two fire extinguishers, provide revised floor plan to plan review showing the office in the back, provide missing canopies for the sprinkler heads.
|
BLD15-04227
| FIRE-Final Inspection | 11/30/2015 | 12/1/2015 | 12/1/2015 10:11:35 AM | A | CANC |
|
|
Rescheduled for tomorrow per contact
|
FIR15-00832
| INSP-Sprinkler Rough-in | 11/30/2015 | 12/1/2015 | 12/1/2015 8:56:46 AM | A | PASS |
|
|
rough-in passed. piping can be covered
|