FIR15-00426
| INSP-Sprinkler Rough-in/Hydro | 11/30/2015 | 12/1/2015 | 12/1/2015 11:13:51 AM | A | PASS |
|
|
200 psi hydrostatic test for overhead fire sprinkler piping passed/complete.
|
FIR15-00724
| INSP-Sprinkler Rough-in | 11/30/2015 | 12/1/2015 | 12/1/2015 10:04:18 AM | A | PASS |
|
|
A wall is installed down the middle of the building, dividing the building into two sections, whole building is under same FIR number. Perfromed rough to cover inspection for hardlids, hardlids on south side of wall approved for cover. Performed rough in inspection for south side of building up to dividing wall, rough in inspection complete. Contractor will schedule rough to cover inspection for gridded area's after heads are cut into place.
|
FIR15-00805
| INSP-Sprinkler Rough-in | 11/30/2015 | 12/1/2015 | 12/1/2015 9:18:40 AM | A | PASS |
|
|
Rough to cover inspection passed/complete, approved for cover.
|
BLD15-01619
| FIRE-Final Inspection | 11/24/2015 | 12/1/2015 | 12/1/2015 8:50:11 AM | A | PART |
|
|
Fire sprinkler FIR permit finaled, no fire alarms for this project. Life fire safety inspection complete, cannot final life fire safety due to racking storage exceeding 8ft in height on the mezzanine level. Need to either remove storage to less than 8ft in elevation or a racking permit will be required to final life fire safety.
|
BLD15-01887
| FIRE-Final Inspection | 12/1/2015 | 12/1/2015 | 12/1/2015 12:00:00 AM | P | CANC |
|
|
Please call when you are going to be inspecting. ###-####. Key is in electrical outlet by front door on front side of home. Phone #: ###-#### >> Inspection requested via web by Forrest LeBaron
|
BLD15-01912
| FIRE-Final Inspection | 11/30/2015 | 12/1/2015 | 11/30/2015 3:18:52 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Frederick Sand Inspection cancelled from web by: Frederick Sand
|
FIR15-00697
| INSP-Sprinkler Rough-in/Hydro | 11/25/2015 | 12/1/2015 | 11/30/2015 9:58:06 AM | A | PASS |
|
|
Previously noted items repaired/complete, rough to cover inspection passed/complete, approved for cover.
|