ELE16-02745
| Final | 12/1/2017 | 12/1/2017 | 12/1/2017 3:16:06 PM | P | PART |
|
|
Final Phone #: ###-#### Inspection requested via web by Kenneth Chapman 3rd floor east hall receps dead, trash room 4sq blank, missing light 2nd floor data room,W. elec room recep, Pannel shedule in house panel,EMT straps Parking garage and Elevator room,
|
ELE17-04050
| Electrical Rough-In | 12/1/2017 | 12/1/2017 | 12/1/2017 1:16:35 PM | P | PASS |
|
|
WE need an underground inspection for today. Thank you Phone #: ###-#### Inspection requested via web by Stacie Tasker OK to cover small section of the first 100ft run of conduits as specified by Tobious
|
ELE17-03421
| Permanent Service | 11/22/2017 | 12/1/2017 | 12/1/2017 1:16:35 PM | P | CANC |
|
|
Jen ###-#### xt.123 (will call you to set up between 2-2:30) needed final
|
ELE17-03421
| Final | 12/1/2017 | 12/1/2017 | 12/1/2017 1:16:34 PM | P | PASS |
|
|
Jen ###-#### xt.123 (will call you to set up between 2-2:30) Final ok
|
ELE17-03837
| Final | 12/1/2017 | 12/1/2017 | 12/1/2017 10:54:49 AM | A | PASS |
|
|
am or pm ok here. Phone #: ###-#### Inspection requested via web by Rex Boyles final ok
|
ELE17-03071
| Final | 11/30/2017 | 12/1/2017 | 12/1/2017 10:20:28 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by John VanZandt final ok
|
ELE17-03421
| Final | 11/28/2017 | 12/1/2017 | 12/1/2017 10:06:52 AM | A | NR |
|
|
Brandy ext 211 Phone #: ###-####
|
ELE17-04025
| Electrical Rough-In | 11/30/2017 | 12/1/2017 | 12/1/2017 10:00:50 AM | A | PASS |
|
|
Reinspection, bath circuit installed Phone #: ###-#### Inspection requested via web by Dan Hobdey up bath and kitchen lighting only ok to cover
|
ELE17-03360
| Final | 11/30/2017 | 12/1/2017 | 12/1/2017 9:54:16 AM | A | FAIL |
|
|
Final on Solar Please call Joey at ###-#### to get in Phone #: ###-#### Inspection requested via web by Paula Gietzen 348.30A Flexable metal conduit shall be securred within 12in of box and every 4 1/2 Ft. 690.31. PV system DC conduits shall be labelled within 3ft of box and every 10 feet.
|
ELE17-01028
| Electrical Rough-In | 11/30/2017 | 12/1/2017 | 12/1/2017 9:06:23 AM | A | PASS |
|
|
Contact: Mike Ennis, ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Lobby only Vestibule not ready Ceilings only ok to cover
|
ELE17-02008
| Electrical Rough-In | 11/30/2017 | 12/1/2017 | 12/1/2017 9:05:25 AM | A | PASS |
|
|
Contact: Mike Ennis, ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Ceilings only ok to cover
|
ELE17-03844
| Electrical Rough-In | 11/30/2017 | 12/1/2017 | 12/1/2017 8:27:22 AM | A | PASS |
|
|
This is an underground inspection. Please feel free to call Luke if you have any questions ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan underground from house to garage only ok to cover
|
ELE17-03845
| Electrical Rough-In | 11/30/2017 | 12/1/2017 | 12/1/2017 8:26:32 AM | A | PASS |
|
|
This is an underground inspection. Please feel free to call Luke if you have any questions ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clay Morgan underground from house to garage only ok to cover
|