FIR17-00667
| INSP-Final Inspection | 12/1/2017 | 12/1/2017 | 12/1/2017 3:01:07 PM | P | CANC |
|
|
Chris or ###-#### Paula Phone #: ###-####
|
FIR17-00611
| INSP-Final Inspection | 11/30/2017 | 12/1/2017 | 12/1/2017 2:00:19 PM | P | PASS |
|
|
Permit finaled
|
FIR16-00821
| INSP-Sprinkler Rough-in | 11/30/2017 | 12/1/2017 | 12/1/2017 1:44:24 PM | P | PASS |
|
|
The piping above the lay-in ceilings in buildings 1 and 2 is ok for cover.
Mikael Phone #: ###-####
|
FIR17-00303
| INSP-Sprinkler Rough-in | 11/30/2017 | 12/1/2017 | 12/1/2017 1:32:13 PM | P | PASS |
|
|
Piping above the hard lids is ok for cover. I noted electrical boxes located close to the pendants that may pose an obstruction problem.
|
BLD17-04363
| FIRE-Final Inspection | 11/30/2017 | 12/1/2017 | 12/1/2017 12:43:31 PM | A | FAIL |
|
|
Need the ceiling tile re-installed or existing sprinkler system modified. Exit signs and emergency lights and fire extinguishers were functional
Russ Phone #: ###-####
|
FIR17-00571
| INSP-Final Inspection | 11/30/2017 | 12/1/2017 | 12/1/2017 10:27:17 AM | A | PASS |
|
|
Permit finaled
Dave Phone #: ###-####
|
FIR17-00690
| INSP-Conference | 12/1/2017 | 12/1/2017 | 12/1/2017 9:11:46 AM | A | DONE |
|
|
Jeff and I spoke about the conditions for final sign offs for the shell and TI permits.
|
FIR17-00690
| INSP-Sprinkler Rough-in | 12/1/2017 | 12/1/2017 | 12/1/2017 9:11:03 AM | A | PASS |
|
|
Piping above the ceilings is ok for cover. Also Need all typical items for final, signs/stickers..ect and also need the pipe sizing to the heads under hvac units and doors addressed and heads changed out at the unit heaters.
wrong cell phone input my apologies. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
FIR17-00275
| INSP-Sprinkler Rough-in | 12/1/2017 | 12/1/2017 | 12/1/2017 9:10:08 AM | A | PASS |
|
|
Need all typical items for final, signs/stickers..ect and also need the pipe sizing to the heads under hvac units and doors addressed and heads changed out at the unit heaters.
|
FIR17-00545
| INSP-Final Inspection | 11/30/2017 | 12/1/2017 | 12/1/2017 7:40:15 AM | A | FAIL |
|
|
Not ready for a final yet but Corridor 199 and the Laundry Room sprinkler piping is ok to cover
Contact Brad Westbrook ###-#### 30 min prior to Fire Final insp Start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR17-00690
| INSP-Sprinkler Rough-in | 11/30/2017 | 12/1/2017 | 12/1/2017 7:05:49 AM | A | FAIL |
|
|
I left two voice messages for contact. I went to project site and made no contact. No inspection performed.
Please call Jeff when available. I will meet you first thing am. Thank you. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
FIR17-00680
| INSP-Final Inspection | 11/28/2017 | 12/1/2017 | 12/1/2017 12:00:00 AM | P | CANC |
|
|
Before 3 - Eric Phone #: ###-#### // 12/1/17 @ 8:15am cancelled per phone call from Crane Alarm//leg
|