FIR17-00602
| INSP-Final Inspection | 11/29/2017 | 12/1/2017 | 12/1/2017 5:00:08 PM | P | PASS |
|
|
Final fire alarm inspection for scope of work passed/complete.
|
FIR17-00255
| INSP-Sprinkler Rough-in | 12/1/2017 | 12/1/2017 | 12/1/2017 1:20:59 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping in lobby area complete, lobby area approved for cover.
|
FIR17-00393
| INSP-Sprinkler Rough-in | 11/30/2017 | 12/1/2017 | 12/1/2017 1:19:59 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, area of work approved for cover.
|
BLD16-01059
| FIRE-Final Inspection | 11/30/2017 | 12/1/2017 | 12/1/2017 10:59:12 AM | A | FAIL |
|
|
Fire alarm modifications not completed at time of inspection, life fire safety inspection stopped.
|
BLD17-02403
| FIRE-Final Inspection | 11/30/2017 | 12/1/2017 | 12/1/2017 10:23:22 AM | A | PASS |
|
|
Final life fire safety inspection for scope of work passed/complete.
|
BLD17-02077
| FIRE-Final Inspection | 12/1/2017 | 12/1/2017 | 12/1/2017 9:02:03 AM | P | PART |
|
|
Fire sprinkler inspection is complete, fire extinguishers are in place with current inspection tags, fire alarm modifications are required and will be installed under FIR17-00702, TCO for life fire safety is authorized for 30 days per conversation with Scott Arellano pending fire alarm inspection when work is completed.
|
FIR17-00684
| INSP-Sprinkler Rough-in | 12/1/2017 | 12/1/2017 | 12/1/2017 8:46:46 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, area of work approved for cover.
|
BLD16-01059
| FIRE-Alarm Testing | 11/30/2017 | 12/1/2017 | 12/1/2017 7:28:46 AM | A | CANC |
|
|
Fire alarm testing/inspection is to be requested by the installing contractor under the associated FIR permit, this request is cancelled.
|