Inspections for the day of: Tuesday, December 10, 2002.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR01-00584 FIR-Aging Inspection12/10/200212/10/200212/10/2002 12:00:00 AM NR
I spoke with Burl Swingle with Allied General and they said they would be calling for an inspection towards the end of the month 12/10/2002 12:28:28 PM
FIR02-00461 INSP-Final Inspection12/6/200212/10/200212/10/2002 12:00:00 AMAFAIL
relocate the two duct smoke detectors out of the Tee intersection and back up into the main HVAC supply. Provide an updated map 12/10/2002 10:43:37 AM
FIR02-00461 INSP-Final Inspection12/6/200212/10/200212/10/2002 12:00:00 AMAFAIL
relocate the two duct smoke detectors out of the Tee intersection and back up into the main HVAC supply. Provide an updated map 12/10/2002 10:43:37 AM
BLD02-01976 FIRE-Final Inspection12/9/200212/10/200212/10/2002 12:00:00 AMAPASS
fire sprinklers and fire life safety finaled 12/10/2002 12:27:07 PM
FIR02-00450 INSP-Final Inspection12/9/200212/10/200212/10/2002 12:00:00 AMAFAIL
The existing fire alarm system does not meet current code requirements. An updated system will be required. Fire alarm plans approved by boise city will be required. No installation work to proceed until plans are approved. No Certificate of Occupancy to be issued until work is completed or a program upgrade agreement has been reach with the boise fire dept.. Contact Dave Miller ###-####. The sprinkler rough-in is OK but the ceilings and the canopies need to be installed 12/10/2002 11:03:34 AM
BLD02-02218 FIRE-Final Inspection12/10/200212/10/200212/10/2002 12:00:00 AMAFAIL
The existing fire alarm system does not meet current code requirements. An updated system will be required. Fire alarm plans approved by boise city will be required. No installation work to proceed until plans are approved. No Certificate of Occupancy to be issued until work is completed or a program upgrade agreement has been reach with the boise fire dept.. Contact Dave Miller ###-####
FIR02-00385 INSP-Conference12/10/200212/10/200212/10/2002 12:00:00 AMPPART
the remaining section of piping from the new riser to the pump room is OK to bury. 12/10/2002 4:08:19 PM
FIR02-00458 INSP-Final Inspection12/10/200212/10/200212/10/2002 12:00:00 AMPPASS
bruce-- ###-####
FIR02-00458 INSP-Final Inspection12/10/200212/10/200212/10/2002 12:00:00 AMPPASS
bruce-- ###-####
BLD02-01461 FIRE-Final Inspection12/10/200212/10/200212/10/2002 12:00:00 AMPFAIL
three emergency lights and two duct detectors do not work. Still need air balance reports 12/10/2002 3:39:14 PM
MIS02-00213 FIR-Final12/10/200212/10/200212/10/2002 12:00:00 AMPFAIL
Repair light in rear hallway, remove thumbturn from warehouse exit door, repair exit sign and emergency light in sales area, provide panic hardware on 2nd exit, repair emergency light in office, provide fire extinguishers. They must be 2A10BC mounted 48" above the finish floor to the handle with an inspection tag 12/10/2002 2:40:26 PM
FIR02-00461 INSP-Alarm Testing12/6/200212/10/200212/6/2002 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 12/06/2002 at 15:38:10. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 12/06/2002 at 15:41:32.