MIS10-00330
| FIR-Conference | 12/10/2010 | 12/10/2010 | 12/15/2010 7:48:26 AM | P | DONE |
|
|
This inspection has been deferred to Tom Gainer with the Boise Fire Dept. for follow up. I also spoke to Mark Sentenno.
|
FIR04-00376
| INSP-Final Inspection | 12/10/2010 | 12/10/2010 | 12/13/2010 2:36:34 PM | P | PASS |
|
|
permit finaled
|
FIR03-00510
| INSP-Final Inspection | 12/7/2010 | 12/10/2010 | 12/10/2010 2:58:34 PM | A | CANC |
|
|
Wrong inspection called in. This one is to be scheduled for next week.
|
FIR10-00300
| INSP-Conference | 12/9/2010 | 12/10/2010 | 12/10/2010 2:30:23 PM | A | DONE |
|
|
I met with Mark from Shilo and we discussed the underground supply line being buried with out any inspections. I left a correction notice referencing IFC 106.2 and 106.3
|
FIR10-00514
| INSP-Sprinkler Rough-in | 12/9/2010 | 12/10/2010 | 12/10/2010 2:28:39 PM | A | FAIL |
|
|
The insulation in the combustible concealed space does not meet 2010 NFPA 13 - 8.15.1.2.17. Blow-in insulation has been used not the batt insulation as required.
|
BLD10-01138
| FIRE-Final Inspection | 12/9/2010 | 12/10/2010 | 12/10/2010 2:27:24 PM | A | CANC |
|
|
Ron wanted to perform this inspection with Forrest but we went over general life safety items such as when the wall were removed that fire alarm coverage and sprinkler head coverage may have been effected.
|
BLD10-02686
| FIRE-Final Inspection | 12/9/2010 | 12/10/2010 | 12/10/2010 2:24:56 PM | A | FAIL |
|
|
Provide sprinkler protection in both coolers. Provide access to the fire sprinkler riser and the fire alarm panel so that annual inspections can be verified.
|
FIR10-00490
| INSP-Final Inspection | 12/9/2010 | 12/10/2010 | 12/10/2010 2:01:08 PM | A | FAIL |
|
|
See the city approved plans for the locations of the deficiencies. They include adding a/v coverage in Offices 105 and 106, providing coverage at the end of a corridor where an existing a/v had been removed, relocating a smoke detector located too close to a supply air diffuser, and setting the correct candella for a strobe in the Vontrol Room on the existing side of this building. No devices were tested. Per plan review as-builts can be provided for the changes.
|
BLD10-01201
| FIRE-Final Inspection | 12/9/2010 | 12/10/2010 | 12/10/2010 1:57:46 PM | A | FAIL |
|
|
II just went over general life safety requirements with Ron since the project related fire alarm permit has failed inspection. One item that was noticed was that on two sliding doors, non-compliant hardware was installed. Ron stated he would remove all of the locking hardware.
|
FIR04-00375
| INSP-Final Inspection | 12/7/2010 | 12/10/2010 | 12/10/2010 11:58:51 AM | A | PASS |
|
|
Permit finaled. The hood suppression system functioned correctly. Alex Phone #: ###-####
|
FIR04-00374
| INSP-Final Inspection | 12/7/2010 | 12/10/2010 | 12/10/2010 11:58:05 AM | A | PASS |
|
|
Permit finaled. The hood suppression system functioned correctly. Alex Phone #: ###-####
|
FIR03-00381
| INSP-Final Inspection | 12/7/2010 | 12/10/2010 | 12/10/2010 11:57:15 AM | A | PASS |
|
|
Permit finaled. The hood suppression system functioned correctly.
|
BLD10-02647
| FIRE-Final Inspection | 12/9/2010 | 12/10/2010 | 12/10/2010 11:55:51 AM | A | PASS |
|
|
life safety passed
|
FIR10-00600
| INSP-Final Inspection | 12/9/2010 | 12/10/2010 | 12/10/2010 11:52:24 AM | A | PASS |
|
|
permit finaled
|
FIR10-00615
| INSP-Final Inspection | 12/10/2010 | 12/10/2010 | 12/10/2010 12:00:00 AM | P | CANC |
|
|
John Phone #: ###-####
|
BLD10-02572
| FIRE-Final Inspection | 12/8/2010 | 12/10/2010 | 12/9/2010 2:51:44 PM | A | FAIL |
|
|
Provide panic hardware on the door and provide verification that the visual effect from the nearby fire alarm devices can be seen within this new room.
|