Inspections for the day of: Monday, December 10, 2012.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-02621 ELE-Aging Inspection12/10/201212/10/201212/10/2012 3:44:56 PM DONE
still under construction
ELE11-01055 Final12/10/201212/10/201212/10/2012 3:43:32 PMPPASS
ok final
ELE11-02586 Final12/10/201212/10/201212/10/2012 3:42:40 PMPPASS
ok final
ELE11-01514 Final12/10/201212/10/201212/10/2012 2:31:06 PMPFAIL
Carl Phone #: ###-#### shall add circuit schedules, gfci for outlets out back
ELE12-02871 Electrical Rough-In12/10/201212/10/201212/10/2012 1:45:57 PMPFAIL
for mech room and other areas not done at prior rough-in Phone #: ###-#### >> Inspection requested via web by joel smith shall provide 6" free , tighten crimps, add stapling
ELE12-02522 Electrical Rough-In12/10/201212/10/201212/10/2012 1:09:40 PMPPART
Please contact Cody for a partial wall cover inspection. Thank you and have a wonderful day! Phone #: ###-#### >> Inspection requested via web by Kevin Perez north end, east and west walls ok, u/g ok if not required to use metal raceway- currently pvc, but may require metal if part of x-ray or patient care area
ELE12-02581 Final12/10/201212/10/201212/10/2012 12:30:05 PMPFAIL
>> Inspection requested via web by joel smith left correction notice, NEC 110.22(A) shall identify disconnects, 408.4 shall provide circuit directory, 110.26 shall provide work space about equipment, 314.28A(2) shall provide correct size enclosure used for angle pulls and splices, 230 shall use service rated equipment
ELE12-02926 Permanent Service12/7/201212/10/201212/10/2012 10:33:40 AMAFAIL
To get the meters set space A space B Phone #: ###-#### >> Inspection requested via web by Brad Baker called, left message, shall identify service and sub-panels with permanent identification
ELE12-02662 Final12/7/201212/10/201212/10/2012 10:00:47 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Dan Surerus ok final, signed card
ELE12-02540 Final12/7/201212/10/201212/10/2012 9:28:06 AMAPASS
Garage code is JAYO enter Phone #: ###-#### >> Inspection requested via web by Zane Robertson ok final
ELE12-02956 Temporary Service12/7/201212/10/201212/10/2012 8:57:58 AMAPASS
Temp Power Phone #: ###-#### >> Inspection requested via web by Zane Robertson t/s u/g n ok
ELE12-02958 Final12/7/201212/10/201212/10/2012 7:50:23 AMACANC
Added Job iD sticker Phone #: ###-#### >> Inspection requested via web by Cevyn Recla see t/s
ELE12-02958 Temporary Service12/10/201212/10/201212/10/2012 7:50:07 AMAPASS
Added Job iD sticker Phone #: ###-#### >> Inspection requested via web by Cevyn Recla t/s u/g n ok