FIR13-00662
| INSP-Final Inspection | 12/10/2013 | 12/10/2013 | 12/10/2013 3:37:26 PM | P | PASS |
|
|
Permit finaled
|
BLD13-01324
| FIRE-Final Inspection | 12/10/2013 | 12/10/2013 | 12/10/2013 3:28:01 PM | P | FAIL |
|
|
Provide self closing doors in stairwell, provide fire extinguishes on both levels and provide building address
|
FIR13-00337
| INSP-Final Inspection | 12/6/2013 | 12/10/2013 | 12/10/2013 2:32:35 PM | P | PASS |
|
|
Permit finaled
|
FIR13-00375
| INSP-Final Inspection | 12/5/2013 | 12/10/2013 | 12/10/2013 2:31:44 PM | P | PASS |
|
|
Permit finaled
|
BLD13-02401
| FIRE-Final Inspection | 12/10/2013 | 12/10/2013 | 12/10/2013 1:59:10 PM | P | PASS |
|
|
Life safety passed
|
FIR13-00383
| INSP-Final Inspection | 12/10/2013 | 12/10/2013 | 12/10/2013 1:58:08 PM | P | PASS |
|
|
Permit finaled
|
FIR13-00497
| INSP-Final Inspection | 12/10/2013 | 12/10/2013 | 12/10/2013 1:57:26 PM | P | PASS |
|
|
Permit finaled
|
FIR13-00468
| INSP-Final Inspection | 12/9/2013 | 12/10/2013 | 12/10/2013 11:11:54 AM | A | FAIL |
|
|
All notification devices were tested today. Some corrections/additions/relocations are needed and have been identified on the city approved plans. Need correct batteries installed in the FACP, verify supervision of NAC panels, verify a/v's in pharmacy, need access controled egress doors connected to the facp, verify interconnection with the pre-action panel and need as-builts.
|
BLD13-02566
| FIRE-Final Inspection | 12/9/2013 | 12/10/2013 | 12/10/2013 10:09:30 AM | A | FAIL |
|
|
No city approved plans on site and no contact on site.
|