Inspections for the day of: Monday, December 10, 2018.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01235 ELE-Aging Inspection12/10/201812/10/201812/18/2018 12:49:30 PM FAIL
Called contractor and he said he would check in to job. Drove by did not look like work still going.
ELE18-04371 Final12/10/201812/10/201812/10/2018 3:12:27 PMPFAIL
Phone #: ###-#### Inspection requested via web by Barbara Szurgot
210.8- Employee led me to receptacles added. Double duplex to right of counter with sink at right end shall be GFCI protected due to with in 6' of sink.
ELE18-04675 Temporary Service12/10/201812/10/201812/10/2018 2:48:52 PMPPASS
Phone #: ###-#### Inspection requested via web by Neal Rumsey t/s u/g n ok
ELE18-04659 Permanent Service12/10/201812/10/201812/10/2018 2:31:05 PMPPASS
Phone #: ###-#### Inspection requested via web by Trevor Soesbe
200 amp meter main on back of house with sub fed panel in garage, also will be changing most receptacles in house on ungrounded circuits. Late start due to late disconnect of power. At time of inspection meter main with mast in place, and ground rods. Sub feed to panel not in yet or any interior work. p/s o/h rec ok
ELE18-03620 Electrical Rough-In12/7/201812/10/201812/10/2018 2:06:25 PMPPASS
Ceiling Inspect please. Phone #: ###-#### Inspection requested via web by CHRIS CARMINE
Conference/break room grid rough in ok cover
ELE18-02353 Final12/8/201812/10/201812/10/2018 2:06:03 PMPPASS
someone will be home in the afternoon Phone #: ###-#### Inspection requested via web by Charles Davis
Master bath light box blanked over tub at time of inspection. Final ok
ELE18-04491 Rough-In Permanent Service12/7/201812/10/201812/10/2018 1:11:38 PMAFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn
334.12- NM cable shall not be installed where subject to damage. Garage small bay between garage exterior lights went under truss.
ELE18-04654 Rough-In Permanent Service12/6/201812/10/201812/10/2018 1:11:04 PMAPASS
Phone #: ###-#### Inspection requested via web by Kevin Heideman
Rough in ok cover p/s u/g n ok
ELE18-04670 Temporary Service12/7/201812/10/201812/10/2018 10:05:01 AMAPASS
Phone #: ###-#### Inspection requested via web by cal crosby t/s u/g n ok
ELE18-04007 Final12/4/201812/10/201812/10/2018 9:20:39 AMAFAIL
Garage Code 2468 Phone #: ###-#### Inspection requested via web by Icon Electric
210.12- All outlets in a bedroom shall have AFCI protection with the AFCI device installed at circuits origin. Up bed.