Inspections for the day of: Monday, December 10, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-04385 Final12/10/201812/10/201812/11/2018 9:28:11 AMACANC
Call proir to arrival ###-####...rescheduled to 12/12/18 per GC
ELE18-04403 Final12/9/201812/10/201812/10/2018 1:05:44 PMPPASS
Please call 30min in advance to ensure access. Phone #: ###-#### Inspection requested via web by Casey Fouts...
floor outlets complete
GFCI protection verified previous inspection
ok to final
ELE18-04562 Electrical Rough-In12/7/201812/10/201812/10/2018 12:47:44 PMPPASS
Phone #: ###-#### Inspection requested via web by Rob Maes...UL listing verified
ELE18-04151 Final12/10/201812/10/201812/10/2018 12:11:00 PMAPASS
Access code 2468
Looking for a final for a C Of O please call if any questions issues or concerns
Thank you for your time and have a great monday Inspection requested via web by leon ramirez..

ok to final...card signed
ELE18-04052 Final12/9/201812/10/201812/10/2018 10:15:05 AMAPASS
Phone #: ###-#### Inspection requested via web by Kyle Dillon.....ok to final
ELE18-02047 Electrical Rough-In12/7/201812/10/201812/10/2018 9:56:27 AMAPASS
Charles Phone #: ###-####...
went over new circuits to kitchen
conference of other future work
ELE18-02047 Conference12/10/201812/10/201812/10/2018 9:55:44 AMAPASS
Charles Phone #: ###-####...
discussed wiring of island outlet
also what would take to do service change-recommend hiring electrician
upstairs complete but still has work in basement to address and will do when have money
discussed extension of permit ok
ELE18-04668 Final12/7/201812/10/201812/10/2018 9:00:22 AMAFAIL
AC unit needs inspected. Key box by front door code 3390 Phone #: ###-#### Inspection requested via web by Darryn Coburn...
1..NM cable not approved to be used in wet or damp locations-334.12(B) A/C and service outlet
2..water heater shall have disconnect or breaker lock out installed
3..all outlets serving kitchen counter tops shall be/have GFCI protection-210.8
4..all garage outlets shall be/have GFCI protection-210.8
5..panel shall be legibally and completely labelled as to its clear, evident, and specific purpose or use-408.4
ELE18-04667 Final12/7/201812/10/201812/10/2018 8:58:16 AMAFAIL
AC unit needs inspected. Key box by front door code 3390 Phone #: ###-#### Inspection requested via web by Darryn Coburn...

1..NM cable not approved to be used in wet or damp location-334.12(B) A/C and service outlet
2..water heater shall have disconnect or breaker lock out installed
3..all outlets serving kitchen counter tops shall be/have GFCI protection-210.8
4..all garage outlets shall be/have GFCI protection-210.8
5..panel shall be legibally and completely labelled as to its clear, evident, and specific purpose or use-408.4