Inspections for the day of: Tuesday, December 10, 2019.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-05515 Rough-in12/10/201912/10/201912/10/2019 4:01:33 PMPPASS
Phone #: 2088718789 >> Inspection requested via mobile web by Albert
- R/I ok
MEC19-05515 Pressure Test12/10/201912/10/201912/10/2019 4:01:19 PMPPASS
Phone #: 2088718789 >> Inspection requested via mobile web by Albert
- 20lb gas pressure test ok
MEC19-05538 Final12/9/201912/10/201912/10/2019 3:53:01 PMPPASS
INSTALLER TRAVIS ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- unit 201 furnace only co ok
MEC19-05557 Rough-in12/10/201912/10/201912/10/2019 3:26:10 PMPFAIL
Phone #: ###-#### Inspection requested via web by Joe Taylor
-condensate line needs to be 3/4" min and of approved material
- only use condensate pump to achieve grade
MEC19-05227 Final12/5/201912/10/201912/10/2019 3:16:11 PMPPASS
Homeowner Kurt Atkins ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
MEC19-05500 Final12/6/201912/10/201912/10/2019 2:43:30 PMPFAIL
Client is available from 12-4pm on Tuesday. JuLee is contact. Phone #: ###-#### Inspection requested via web by Andrea Grigsby
- furnace flue needs b vent through ceiling and roof replaced and extended through roof and terminate with listed cap/ roof assembly to proper height based on roof slope
MEC19-05560 Final12/10/201912/10/201912/10/2019 1:50:52 PMPPASS
Phone #: ###-#### Inspection requested via web by max sanders
- final ok
MEC19-05560 Pressure Test12/10/201912/10/201912/10/2019 1:50:40 PMPPASS
Phone #: ###-#### Inspection requested via web by max sanders
- 20lb gas pressure test ok
MEC19-05541 Pressure Test12/9/201912/10/201912/10/2019 1:13:17 PMPFAIL
Please call Dan on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- gauge would not zero
MEC19-05541 Final12/9/201912/10/201912/10/2019 1:12:43 PMPCANC
Please call Dan on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
MEC19-05089 Final12/5/201912/10/201912/10/2019 12:52:07 PMPCANC
Homeowner Jon Corlett ###-#### Phone #: ###-#### >> Inspection requested via web by Mary LaFayette Inspection cancelled from web by: Mary LaFayette
MEC19-05486 Final12/9/201912/10/201912/10/2019 11:20:33 AMAPASS
Inspection requested via web by Jeff Glynn
MEC19-05196 Rough-in12/9/201912/10/201912/10/2019 11:04:30 AMAFAIL
Phone #: ###-#### Inspection requested via web by Benny Arreola
- need to access to furnace and equipment in attic
- man J approved and onsite
- CSST near range needs full strikers plates installed in wall studs
- where is mechanically vented crawls intake coming from within the house?
MEC19-05196 Pressure Test12/9/201912/10/201912/10/2019 11:01:29 AMAFAIL
Phone #: ###-#### Inspection requested via web by Benny Arreola
- gas pressure test needs to be a 60lb test on a 100lb
MEC19-05152 Final12/9/201912/10/201912/10/2019 10:29:02 AMAFAIL
call for lock box code // Santiago Phone #: ###-####
- furnace needs electrical wiring finished
- dryer vent needs finished
- furnace flue and all work in attic has not been inspected. need access
MEC19-05152 Pressure Test12/9/201912/10/201912/10/2019 10:24:27 AMAPASS
call for lock box code // Santiago Phone #: ###-####
- 20lb gas pressure test ok
MEC19-05350 Final12/9/201912/10/201912/10/2019 10:08:43 AMAFAIL
Our Salesman will meet the inspector at the location. We are just down the road from location please call ahead or when arrived and will have the salesman there. Thank you Phone #: ###-#### Inspection requested via web by Loren Bailey
- line set in attic needs insulation filled in and fixed
- secondary drain needs a wet switch
- line set needs UV protection and locking caps installed on three service ports
MEC19-02174 Mec-Aging Inspection12/10/201912/10/201912/10/2019 8:02:07 AM FAIL
Permit has not been active since being issued on 5-23-19. Schedule inspection with homeowner if work is finished. Permit will expire at next mechanical aging inspection if not active.
MEC19-02173 Mec-Aging Inspection12/10/201912/10/201912/10/2019 8:00:07 AM FAIL
Permit has not been active since being issued on 5-23-19. Schedule inspection with homeowner if work is finished. Permit will expire at next mechanical aging inspection if not active.
MEC18-02236 Mec-Aging Inspection12/10/201912/10/201912/10/2019 7:58:37 AM FAIL
Permit has not been active since talking with the contractor. Type1 hood still has corrections that need made. Schedule inspection if corrections have been made. Permit will expired at next mechanical aging inspection if not active.