Inspections for the day of: Wednesday, December 11, 2002.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE01-02928 ELE-Aging Inspection12/11/200212/11/200212/11/2002 12:00:00 AM PART
SUC 12/11/2002 10:34:36 AM
ELE01-03506 ELE-Aging Inspection12/11/200212/11/200212/11/2002 12:00:00 AM PART
stopped at job site they need to install #8 equipment grd for voltage drop 20 amp circuit with #8 phase and neutral 250.122(B) called Leon at Tri state he will check it out and get back with me and call for final 12/11/2002 6:45:34 PM
ELE01-03573 ELE-Aging Inspection12/11/200212/11/200212/11/2002 12:00:00 AM PART
stopped at job site called left message 12/11/2002 12:18:16 PM
ELE01-03782 ELE-Aging Inspection12/11/200212/11/200212/11/2002 12:00:00 AM PART
called contractor they wiil address it 12/16/2002 3:15:30 PM
12/16/2002 3:15:33 PM
ELE02-03826 Temporary Service12/10/200212/11/200212/11/2002 12:00:00 AMAPASS
dan ###-####

t/s u/g new ok 12/11/2002 11:33:58 AM
ELE02-03719 Temporary Service12/10/200212/11/200212/11/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 12/10/2002 at 15:06:33. Contact: ###-####.

t/s u/g new ok 12/11/2002 11:01:09 AM
ELE01-03996 Final12/10/200212/11/200212/11/2002 12:00:00 AMAFAIL
###-####- joann-call 1st before insp -re-insp cor. posted called 110.26 shall provide required clearence in front of p/s, 250.140,142(B) needs 4 wire cable for range and dryer from sub panel or terminate range and dryer 3 wire cables at p/s 12/11/2002 2:24:09 PM
ELE02-03831 Temporary Service12/11/200212/11/200212/11/2002 12:00:00 AMPPASS
kirk- ###-#### t/s u/g new ok 12/11/2002 2:47:07 PM
ELE02-01270 Electrical Rough-In12/11/200212/11/200212/11/2002 12:00:00 AMPPART
NEEDS EXTENION \\###-#### ok for extenion 12/11/2002 2:29:23 PM
ELE02-03772 Rough-In Permanent Service12/11/200212/11/200212/11/2002 12:00:00 AMPPART
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung r/i only no p/s needs bond to water system called 12/11/2002 4:54:27 PM
ELE02-03786 Rough-In Permanent Service12/11/200212/11/200212/11/2002 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 12/11/2002 at 09:04:48. Contact: ###-####. see added r/i inspection cor. posted for p/s , 110.3(A) replace ringed wire meter and main breaker, called 12/11/2002 3:20:47 PM
ELE02-03586 Electrical Rough-In12/11/200212/11/200212/11/2002 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 12/11/2002 at 10:32:14. Contact: ###-####. cor. posted 300.14, 250.66 bond water with #4 200.7 old wiring white shall not be used as phase wire, 210.70 light fixture shall light back area, 314.23 cutin boxes shall be rigidly mounted in finish surfaces, 314.20 boxes set back more than 1/4 inch check out all old wiring 12/11/2002 5:56:44 PM
ELE02-03786 Electrical Rough-In12/11/200212/11/200212/11/2002 12:00:00 AMPPASS
r/i ok only cor. posted for p/s
ELE02-01402 Final12/10/200212/11/200212/10/2002 12:00:00 AMACANC
###-#### mike Disp set to [CANC] by a contractor via Hello! on 12/10/2002 at 11:43:56.