Inspections for the day of: Wednesday, December 11, 2002.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00461 INSP-Final Inspection12/10/200212/11/200212/11/2002 12:00:00 AMAPASS
fire alarm finaled 12/11/2002 8:48:21 AM
FIR02-00359 INSP-Alarm Testing12/10/200212/11/200212/11/2002 12:00:00 AMAFAIL
the NAC panel in electrical room 125 does not report a trouble when ac power is off and the standby current draw exceeds the calculations, two exit signs in the open office 126 do not work, smoke detectors at the top of the elevator shaft does not recall to the first floor but since there are no sprinklers at the top of the elevator the heat and the smoke should be removed, the heat detector is more than 24" from the sprinkler pendant, 12/11/2002 12:56:02 PM 12/11/2002 12:56:39 PM
BLD02-01461 FIRE-Final Inspection12/11/200212/11/200212/11/2002 12:00:00 AMAPASS
fire life/safety finaled 12/11/2002 2:11:05 PM
BLD02-01969 FIRE-Final Inspection12/11/200212/11/200212/11/2002 12:00:00 AMAPASS
Fire alarm system finaled
BLD02-01720 FIRE-Final Inspection12/10/200212/11/200212/11/2002 12:00:00 AMAPASS
ok for perm occupancy 12/11/2002 12:44:30 PM
BLD02-00502 FIRE-Final Inspection12/10/200212/11/200212/11/2002 12:00:00 AMPFAIL
need to test the emergency lights in the west stair well. Contractor (nobody) was not on site 12/11/2002 1:41:11 PM
BLD02-02323 FIRE-Final Inspection12/10/200212/11/200212/11/2002 12:00:00 AMPPASS
Fire life/safety finaled. Structural inspector to please verify that the "door to remain unlocked during business hours" stickers are installed on both doors 12/11/2002 2:05:10 PM
FIR02-00385 INSP-Conference12/11/200212/11/200212/11/2002 12:00:00 AMPPART
all underground is ok to cover except for the section that will tie to the united water stub-in 12/11/2002 3:51:27 PM
FIR02-00332 INSP-Sprinkler Rough-in/Hydro12/11/200212/11/200212/11/2002 12:00:00 AMPCANC
the fire alarm contractor could not make it to the inspection 12/11/2002 3:42:44 PM
BLD02-00751 FIRE-Final Inspection12/11/200212/11/200212/11/2002 12:00:00 AMPFAIL
repair the exit signs and test the duct smoke detectors 12/11/2002 3:02:52 PM
BLD02-00751 FIRE-Final Inspection12/11/200212/11/200212/11/2002 12:00:00 AMPFAIL
repair the exit signs and test the duct smoke detectors 12/11/2002 3:02:52 PM