Inspections for the day of: Monday, December 11, 2006.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00783 Final12/11/200612/11/200612/11/2006 3:38:45 PMPPASS
laberta ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
ELE06-03237 Final12/11/200612/11/200612/11/2006 3:22:59 PMPPASS
Casey; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett ok to final
ELE06-02657 Final12/8/200612/11/200612/11/2006 2:58:49 PMPPASS
ready for final! thank you; Phone #: ###-#### Internet Inspection Request from: Loren Ramsey ok to final, called contr, no card to sign
ELE06-04548 Temporary Service12/11/200612/11/200612/11/2006 2:20:01 PMPPASS
George; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett t/s o/h n ok
ELE06-02944 Rough-In Permanent Service12/11/200612/11/200612/11/2006 1:37:15 PMPPASS
don - note: underground rough-in also ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith u/g ok to cover from service to junction box, p/s u/g n ok
ELE06-02944 Permanent Service12/11/200612/11/200612/11/2006 1:35:57 PMPCANC
don - note: underground rough-in also ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith wrong type request, see rip
ELE06-02792 Final12/11/200612/11/200612/11/2006 1:27:52 PMPFAIL
Rich Note: Call 1/2 prior to insp ; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett met owner, nec 210.8(A)(2) garage recpts shall be gfci protected, 408.4 circuit directory shall be done, 312.5 abrasion protection shall be provided for conductors entering enclosures, 110.12(A) unused openings shall be closed in panel
ELE06-02364 Conference12/8/200612/11/200612/11/2006 11:39:59 AMADONE
WAYNE nOTE: EARLY EARLY; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles met contr, talked about application of buck- boost transformers, and pool lights. Lights ok, don't need gfci.
ELE06-04522 Final12/11/200612/11/200612/11/2006 9:05:50 AMAPASS
ok to final
ELE06-04522 Electrical Rough-In12/8/200612/11/200612/11/2006 9:05:12 AMAPASS
Work performed by Kyle Sharp.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz ric ok
ELE06-04525 Final12/8/200612/11/200612/11/2006 8:39:20 AMAPASS
Please contact Dan, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters talked to elect, no ri, installed light in exst hard lid, exst ckt, ok to final