Inspections for the day of: Monday, December 11, 2006.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00912 INSP-Final Inspection12/11/200612/11/200612/11/2006 3:33:33 PMPPASS
Fire alarm work passed field inspection. Record of Completion forms to be delivered for signature as agreed.
FIR06-00890 INSP-Sprinkler Rough-in12/11/200612/11/200612/11/2006 3:30:40 PMPPART
OH sprinkler rough-in is good for cover at the drop ceilings in the areas as noted on approved plan set.
FIR06-00759 INSP-Sprinkler Rough-in/Hydro12/11/200612/11/200612/11/2006 3:26:48 PMPPART
Hydrostatic test of the new class1 standpipe passed inspection, standpipe installation is satisfactory.
FIR06-00595 INSP-Alarm Testing12/6/200612/11/200612/11/2006 3:24:35 PMAPART
2nd floor SW quad alarm test completed satisfactory.
BLD06-02349 FIRE-Conference12/8/200612/11/200612/11/2006 3:22:40 PMADONE
On site conference to discuss life safety items including exit signage, emergency lighting, fire extinguishers, alarm and hood suppression permits.