Inspections for the day of: Monday, December 11, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-00635 FIRE-Final Inspection12/11/200612/11/200612/12/2006 3:01:40 PMPFAIL
I need verification that a permit has been pulled for the fuel system as per the review comments. I need verification that the grading permit has been completed as per the review comments. Emergency lights need to be installed in the small room as discussed. Exit discharge lighting needs to be provided at the new east exit as per the review comments. The fire alarm permit needs to be finaled.
FIR05-00836 INSP-Final Inspection12/11/200612/11/200612/12/2006 2:58:44 PMPFAIL
Waiting for the second floor NAC panel's new card to be installed and the interconnection with the FACP to be tested.
BLD06-02317 FIRE-Final Inspection12/11/200612/11/200612/11/2006 4:53:51 PMPCANC
Not ready for inspection until fire alarm is complete
BLD06-00051 FIRE-Final Inspection12/11/200612/11/200612/11/2006 4:53:28 PMPCANC
Not ready for inspection until fire alarm is complete
FIR05-00536 INSP-Sprinkler Rough-in12/11/200612/11/200612/11/2006 3:32:40 PMPPASS
Flow of the most remote standpipe passed. Actual flow was 1,292 gallons.
FIR05-00536 INSP-Alarm Testing12/8/200612/11/200612/11/2006 3:30:13 PMPCANC
Wrong type of inspection called in.
FIR06-00318 INSP-Final Inspection12/11/200612/11/200612/11/2006 3:12:28 PMPPASS
Permit finaled. Underground flushed and alarms tested.
FIR06-00338 INSP-Final Inspection12/11/200612/11/200612/11/2006 3:12:13 PMPPASS
Permit finaled. Underground flushed and alarms tested.
FIR06-00843 INSP-Sprinkler Rough-in12/11/200612/11/200612/11/2006 2:35:24 PMPPASS
Sprinkler piping is ok to cover in this building.
FIR06-00841 INSP-Sprinkler Rough-in12/11/200612/11/200612/11/2006 2:28:08 PMPPASS
Sprinkler piping is ok to cover.
FIR06-00909 INSP-Final Inspection12/8/200612/11/200612/11/2006 2:04:54 PMAFAIL
A door security magnet has been attached to the fire alarm panel and is not swhown on the plans. All other items have been tested satisfactory.
BLD06-02482 FIRE-Final Inspection12/11/200612/11/200612/11/2006 10:48:59 AMPPASS
Life safety finaled