Inspections for the day of: Thursday, December 11, 2008.
Number of inspections: 26
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC07-01432 General Inspection12/11/200812/11/200812/11/2008 4:06:50 PMPPASS
looked ok
ESC08-00824 General Inspection12/11/200812/11/200812/11/2008 4:05:14 PMPPASS
looked ok
ELE08-03183 Temporary Service12/11/200812/11/200812/11/2008 4:04:06 PMPFAIL
called, left correction notice, NEC 110.12(B) there shall be no damaged parts, 590.6(B) 50A receptacle shall be protected by gfci
ELE08-03182 Temporary Service12/11/200812/11/200812/11/2008 4:01:02 PMPCANC
ELE08-03182 Temporary Service12/11/200812/11/200812/11/2008 3:51:29 PMPFAIL
called left correction notice, NEC 110.12(B) there shall be no broken parts, 110.14(A) equipment ground terminal shall be attached to panel, no esc this project
ESC08-00965 General Inspection12/11/200812/11/200812/11/2008 3:30:36 PMPPASS
looked ok
ESC08-00817 General Inspection12/11/200812/11/200812/11/2008 3:29:38 PMAPASS
looked ok
ESC07-01278 Complaint Inspection12/11/200812/11/200812/11/2008 3:28:32 PMAPASS
looked ok
ESC08-00802 General Inspection12/11/200812/11/200812/11/2008 3:27:30 PMAPASS
looked ok
ELE08-03181 Temporary Service12/11/200812/11/200812/11/2008 3:20:45 PMPFAIL
called, left correction notice,NEC110.12(B) there shall be no broken parts- receptacle
ELE08-03177 Temporary Service12/11/200812/11/200812/11/2008 3:18:05 PMPFAIL
called contractor, left correction notice,NEC 119.12(B) there shall be no broken parts- receptacles, 250.24(A)(1) shall connect gec to grounded service conductor terminal, no esc this project
ELE08-02423 Permanent Service12/11/200812/11/200812/11/2008 3:13:28 PMPPASS
JASON Phone #: ###-#### Internet Inspection Request from: Sean DeLacy p/s u/g n ok
ELE08-03177 Temporary Service12/11/200812/11/200812/11/2008 3:05:17 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Joe Thomas Inspection cancelled from web by: Joe Thomas
ELE08-03181 Temporary Service12/11/200812/11/200812/11/2008 3:05:07 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Joe Thomas Inspection cancelled from web by: Joe Thomas
ELE08-03182 Temporary Service12/11/200812/11/200812/11/2008 3:04:57 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Joe Thomas Inspection cancelled from web by: Joe Thomas
ELE08-03183 Temporary Service12/11/200812/11/200812/11/2008 3:04:44 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Joe Thomas Inspection cancelled from web by: Joe Thomas
ELE08-03209 Rough-In Permanent Service12/11/200812/11/200812/11/2008 2:26:18 PMPFAIL
brandon Phone #: ###-#### called, left correction notice, NEC 300.14 shall have at least 6" free conductor length at outlet boxes, 210.52(A) shall provide receptacle in south kitchen wall, 110.12(B) shall not use broken box in bathroom ( clamp for nm broken out),110.11 shall not have re-bar exposed to elements for gec, 250.94 shall provide intersystem bonding bar, BCC house shall be brought up to code, Note: corrections shall be made within 2 working days
ELE08-02921 Final12/11/200812/11/200812/11/2008 1:26:28 PMPPASS
Mark Zurdurbin call mark for access at ###-####. Thanks, Andrea. Internet Inspection Request from: Andrea Creek called contractor, ok to final
ELE07-03975 Final12/11/200812/11/200812/11/2008 12:42:58 PMPPART
joe - partial Phone #: ###-#### ok to final alf dining room, halls, and aid station
ELE08-03188 Temporary Service12/11/200812/11/200812/11/2008 11:36:06 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Joe Thomas t/s u/g n ok, no esc this project
ELE08-03187 Temporary Service12/11/200812/11/200812/11/2008 10:23:42 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Joe Thomas t/s u/g n ok, no esc this project
ELE08-03189 Temporary Service12/11/200812/11/200812/11/2008 10:13:12 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Joe Thomas t/s u/g n ok, no esc this project
ELE08-02912 Final12/10/200812/11/200812/11/2008 9:46:07 AMAPASS
Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA ok to final
ELE08-03102 Final12/11/200812/11/200812/11/2008 8:59:35 AMAFAIL
Scheduled by a contractor via Hello! on 12/11/2008 at 6:49:02 AM. Contact: ###-####. called contractor, BCC all work shall be done before inspection- garage lights
ELE08-03126 Final12/10/200812/11/200812/11/2008 8:43:06 AMAPASS
ready for final Phone #: ###-#### Internet Inspection Request from: gary batten ok to final, no esc this project
ELE08-02530 Final12/10/200812/11/200812/11/2008 8:10:18 AMAPASS
Completed Corrections Phone #: ###-#### Internet Inspection Request from: Therrin Robertson corrections made, ok to final, signed occupancy card