ESC07-01432
| General Inspection | 12/11/2008 | 12/11/2008 | 12/11/2008 4:06:50 PM | P | PASS |
|
|
looked ok
|
ESC08-00824
| General Inspection | 12/11/2008 | 12/11/2008 | 12/11/2008 4:05:14 PM | P | PASS |
|
|
looked ok
|
ELE08-03183
| Temporary Service | 12/11/2008 | 12/11/2008 | 12/11/2008 4:04:06 PM | P | FAIL |
|
|
called, left correction notice, NEC 110.12(B) there shall be no damaged parts, 590.6(B) 50A receptacle shall be protected by gfci
|
ELE08-03182
| Temporary Service | 12/11/2008 | 12/11/2008 | 12/11/2008 4:01:02 PM | P | CANC |
|
|
|
ELE08-03182
| Temporary Service | 12/11/2008 | 12/11/2008 | 12/11/2008 3:51:29 PM | P | FAIL |
|
|
called left correction notice, NEC 110.12(B) there shall be no broken parts, 110.14(A) equipment ground terminal shall be attached to panel, no esc this project
|
ESC08-00965
| General Inspection | 12/11/2008 | 12/11/2008 | 12/11/2008 3:30:36 PM | P | PASS |
|
|
looked ok
|
ESC08-00817
| General Inspection | 12/11/2008 | 12/11/2008 | 12/11/2008 3:29:38 PM | A | PASS |
|
|
looked ok
|
ESC07-01278
| Complaint Inspection | 12/11/2008 | 12/11/2008 | 12/11/2008 3:28:32 PM | A | PASS |
|
|
looked ok
|
ESC08-00802
| General Inspection | 12/11/2008 | 12/11/2008 | 12/11/2008 3:27:30 PM | A | PASS |
|
|
looked ok
|
ELE08-03181
| Temporary Service | 12/11/2008 | 12/11/2008 | 12/11/2008 3:20:45 PM | P | FAIL |
|
|
called, left correction notice,NEC110.12(B) there shall be no broken parts- receptacle
|
ELE08-03177
| Temporary Service | 12/11/2008 | 12/11/2008 | 12/11/2008 3:18:05 PM | P | FAIL |
|
|
called contractor, left correction notice,NEC 119.12(B) there shall be no broken parts- receptacles, 250.24(A)(1) shall connect gec to grounded service conductor terminal, no esc this project
|
ELE08-02423
| Permanent Service | 12/11/2008 | 12/11/2008 | 12/11/2008 3:13:28 PM | P | PASS |
|
|
JASON Phone #: ###-#### Internet Inspection Request from: Sean DeLacy p/s u/g n ok
|
ELE08-03177
| Temporary Service | 12/11/2008 | 12/11/2008 | 12/11/2008 3:05:17 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas Inspection cancelled from web by: Joe Thomas
|
ELE08-03181
| Temporary Service | 12/11/2008 | 12/11/2008 | 12/11/2008 3:05:07 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas Inspection cancelled from web by: Joe Thomas
|
ELE08-03182
| Temporary Service | 12/11/2008 | 12/11/2008 | 12/11/2008 3:04:57 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas Inspection cancelled from web by: Joe Thomas
|
ELE08-03183
| Temporary Service | 12/11/2008 | 12/11/2008 | 12/11/2008 3:04:44 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas Inspection cancelled from web by: Joe Thomas
|
ELE08-03209
| Rough-In Permanent Service | 12/11/2008 | 12/11/2008 | 12/11/2008 2:26:18 PM | P | FAIL |
|
|
brandon Phone #: ###-#### called, left correction notice, NEC 300.14 shall have at least 6" free conductor length at outlet boxes, 210.52(A) shall provide receptacle in south kitchen wall, 110.12(B) shall not use broken box in bathroom ( clamp for nm broken out),110.11 shall not have re-bar exposed to elements for gec, 250.94 shall provide intersystem bonding bar, BCC house shall be brought up to code, Note: corrections shall be made within 2 working days
|
ELE08-02921
| Final | 12/11/2008 | 12/11/2008 | 12/11/2008 1:26:28 PM | P | PASS |
|
|
Mark Zurdurbin call mark for access at ###-####. Thanks, Andrea. Internet Inspection Request from: Andrea Creek called contractor, ok to final
|
ELE07-03975
| Final | 12/11/2008 | 12/11/2008 | 12/11/2008 12:42:58 PM | P | PART |
|
|
joe - partial Phone #: ###-#### ok to final alf dining room, halls, and aid station
|
ELE08-03188
| Temporary Service | 12/11/2008 | 12/11/2008 | 12/11/2008 11:36:06 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas t/s u/g n ok, no esc this project
|
ELE08-03187
| Temporary Service | 12/11/2008 | 12/11/2008 | 12/11/2008 10:23:42 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas t/s u/g n ok, no esc this project
|
ELE08-03189
| Temporary Service | 12/11/2008 | 12/11/2008 | 12/11/2008 10:13:12 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas t/s u/g n ok, no esc this project
|
ELE08-02912
| Final | 12/10/2008 | 12/11/2008 | 12/11/2008 9:46:07 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA ok to final
|
ELE08-03102
| Final | 12/11/2008 | 12/11/2008 | 12/11/2008 8:59:35 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 12/11/2008 at 6:49:02 AM. Contact: ###-####. called contractor, BCC all work shall be done before inspection- garage lights
|
ELE08-03126
| Final | 12/10/2008 | 12/11/2008 | 12/11/2008 8:43:06 AM | A | PASS |
|
|
ready for final Phone #: ###-#### Internet Inspection Request from: gary batten ok to final, no esc this project
|
ELE08-02530
| Final | 12/10/2008 | 12/11/2008 | 12/11/2008 8:10:18 AM | A | PASS |
|
|
Completed Corrections Phone #: ###-#### Internet Inspection Request from: Therrin Robertson corrections made, ok to final, signed occupancy card
|