FIR08-00796
| INSP-Sprinkler Rough-in/Hydro | 12/10/2008 | 12/11/2008 | 12/12/2008 6:14:00 PM | A | PART |
|
|
Rough-in inspection passed, one missing hanger added while on site. Hydrostatic test failed due to pressure loss at the guage. Site notes per TF.
|
FIR08-00278
| INSP-Final Inspection | 12/11/2008 | 12/11/2008 | 12/11/2008 6:14:36 PM | P | PASS |
|
|
Fire alarm permit doc finaled.
|
FIR08-00512
| INSP-Final Inspection | 12/11/2008 | 12/11/2008 | 12/11/2008 6:10:41 PM | P | PASS |
|
|
Fire alarm permit doc finaled.
|
FIR08-00614
| INSP-Final Inspection | 12/10/2008 | 12/11/2008 | 12/11/2008 6:08:43 PM | P | PASS |
|
|
Fire sprinkler permit work passed final inspection, contractor to provide stock of spare sprinklers per NFPA 13 req. of the type installed.
|
FIR07-01042
| INSP-Sprinkler Rough-in/Hydro | 12/10/2008 | 12/11/2008 | 12/11/2008 6:06:03 PM | P | PART |
|
|
24 hr. air testing completed and passed for both dry systems.
|
FIR08-00703
| INSP-Alarm Testing | 12/11/2008 | 12/11/2008 | 12/11/2008 6:02:27 PM | P | PASS |
|
|
Fire alarm testing passed.
|
FIR08-00721
| INSP-Final Inspection | 12/10/2008 | 12/11/2008 | 12/11/2008 12:55:28 PM | A | PASS |
|
|
Fire sprinkler permit work passed field inspection, permit finaled. NOTE: contractor agreed to install head guards at two locations where sprinklers are below 7' AFF and subject to mechanical damage.
|
BLD08-02297
| FIRE-Final Inspection | 12/10/2008 | 12/11/2008 | 12/11/2008 12:50:52 PM | A | PASS |
|
|
Fire life safety completed satisfactory, noted three missing doors to be provided as agreed.
|
BLD08-02296
| FIRE-Final Inspection | 12/10/2008 | 12/11/2008 | 12/11/2008 12:49:43 PM | A | PASS |
|
|
Fire life safety inspection passed, suite numbers on site and to be posted prior to final as discussed.
|
FIR08-00018
| INSP-Sprinkler Rough-in/Hydro | 12/10/2008 | 12/11/2008 | 12/11/2008 12:48:47 PM | A | FAIL |
|
|
Rough-in inspection for cover at the 9th floor failed due to an overspaced pendent, one overspaced SW head, need an additonal hanger at one location, noted close proximity between some pendent heads and electrical junction boxes at the ceiling which may create an obstruction depending upon the fixture installed- see spacing requirements per NFPA 13R 6.8.1.5.3.2, also need to maintain min. distances from heat sources per 6.7.7.1.5.3. Marked locations on as-built plans, need stamped resubmittals prior to final cover approvals.
|