Inspections for the day of: Friday, December 11, 2009.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00471 INSP-Final Inspection12/11/200912/11/200912/11/2009 4:39:44 PMPPASS
Fire alarm permit work passed final field inspection.
BLD09-01460 FIRE-Final Inspection12/11/200912/11/200912/11/2009 4:38:35 PMPPASS
Fire life safety inspection completed satisfactory.
FIR09-00193 INSP-Final Inspection12/10/200912/11/200912/11/2009 4:36:36 PMAPART
Inspection passed with the exception of RTU 26 in need of repair, and RTU 1 without access to complete testing, list of signals dated 12/10 and 12/11 to be provided at next inspection and prior to final.
FIR09-00503 INSP-Final Inspection12/9/200912/11/200912/11/2009 2:03:53 PMAFAIL
All correction notice items are finished with the exception of one HVAC unit which failed to shutdown upon smoke detection.
BLD09-01689 FIRE-Final Inspection12/11/200912/11/200912/11/2009 1:59:44 PMPPASS
Fire life safety approved pending installation of "door to remain..... " signage at the main entry/exit, and seal at the door to the med. gas closet- to be completed prior to structural final inspection as discussed.
FIR09-00627 INSP-Final Inspection12/11/200912/11/200912/11/2009 1:56:39 PMPPASS
Correction notice items verified for compliance, fire sprinkler permit finaled.
BLD09-01849 FIRE-Final Inspection12/10/200912/11/200912/11/2009 1:55:31 PMAPASS
Fire life safety inspection completed satisfactory.
BLD09-01924 FIRE-Final Inspection12/10/200912/11/200912/11/2009 1:54:39 PMAPASS
Fire life safety site inspection passed, mag locks at stairway exit doors have been removed.
FIR09-00634 INSP-Final Inspection12/11/200912/11/200912/11/2009 1:53:41 PMPPASS
Fire sprinkler permit approved for final status.
FIR08-00819 INSP-Final Inspection12/10/200912/11/200912/11/2009 1:52:44 PMANR
Pending satisfactory netcon rating.
BLD09-02030 FIRE-Final Inspection12/10/200912/11/200912/11/2009 1:51:39 PMAPASS
Fire life safety inspection for the first floor okayed for occupancy per permit documents.