ELE12-03067
| ELE-Aging Inspection | 12/11/2014 | 12/11/2014 | 12/15/2014 11:42:13 AM | | DONE |
|
|
Spoke to Dan, he will check on it.
|
ELE14-03414
| Final | 12/11/2014 | 12/11/2014 | 12/11/2014 2:07:01 PM | P | FAIL |
|
|
Please call ahead, homeowner not home all day - Brady Phone #: ###-#### More conference than inspection all breakers need to be labeled arc fault protection required for smoke detectors and bedrooms need all switch and outlet plates installed need service light for water heater a/c wiring needs replaced, aluminum flex and nm cable not allwed outdoors, max breaker size allowed is 25 amp
|
ELE14-00212
| Final | 12/10/2014 | 12/11/2014 | 12/11/2014 1:36:13 PM | P | PASS |
|
|
Please call the homeowner Amy ###-#### for access and please call Clay to meet you there ###-####. Thank You!!!! Phone #: ###-#### Inspection requested via web by Clay Morgan corrections made, final OK
|
ELE14-02767
| Final | 12/11/2014 | 12/11/2014 | 12/11/2014 1:05:44 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Lars Johnson called Lars 210.8.7. GFI protection required within 6 foot from edge of sinks 422.31 DIsxonnecting means required for fixed appliances, furnace 334.15 NM cable shall be protected from physical damage, furnace
|
ELE14-03403
| Final | 12/10/2014 | 12/11/2014 | 12/11/2014 12:21:32 PM | A | NH |
|
|
wire gas fireplace Phone #: ###-#### Inspection requested via web by PAT MILLER no access, called pat
|
ELE14-03403
| Electrical Rough-In | 12/10/2014 | 12/11/2014 | 12/11/2014 12:21:31 PM | A | NH |
|
|
Phone #: ###-#### Inspection requested via web by PAT MILLER no access, called pat
|
ELE14-03125
| Final | 12/10/2014 | 12/11/2014 | 12/11/2014 9:54:57 AM | A | PASS |
|
|
code is 2468 on garage. thanks Phone #: ###-#### Inspection requested via web by Darryn Coburn FInal OK
|
ELE12-01040
| Final | 12/10/2014 | 12/11/2014 | 12/11/2014 9:26:10 AM | A | PASS |
|
|
Donald Phone #: ###-#### final ok
|
ELE13-03535
| Final | 12/8/2014 | 12/11/2014 | 12/11/2014 9:10:01 AM | A | FAIL |
|
|
Phone #: 2088661213 >> Inspection requested via mobile web by Todd Nelson spoke with owner about corrections romex must be secured within 12 inches of box permanently attached appliances shall have means of disconnect, ovens, d/w, rangehood, micro romex shall be subject to damage, provide cover
|
ELE14-03081
| Final | 12/10/2014 | 12/11/2014 | 12/11/2014 8:32:34 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by David Seilheimer corrections made, final OK
|
ELE14-03411
| Final | 12/10/2014 | 12/11/2014 | 12/11/2014 8:14:49 AM | A | PASS |
|
|
David-ask for Shelley Phone #: ###-#### see rough inspection
|
ELE14-03411
| Electrical Rough-In | 12/10/2014 | 12/11/2014 | 12/11/2014 8:14:23 AM | A | PASS |
|
|
David Phone #: ###-####-ask fopr Shelley UL listed non-ballsted LED lamps, RI OK
|