Inspections for the day of: Thursday, December 11, 2014.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-03067 ELE-Aging Inspection12/11/201412/11/201412/15/2014 11:42:13 AM DONE
Spoke to Dan, he will check on it.
ELE14-03414 Final12/11/201412/11/201412/11/2014 2:07:01 PMPFAIL
Please call ahead, homeowner not home all day - Brady Phone #: ###-####
More conference than inspection
all breakers need to be labeled
arc fault protection required for smoke detectors and bedrooms
need all switch and outlet plates installed
need service light for water heater
a/c wiring needs replaced, aluminum flex and nm cable not allwed outdoors, max breaker size allowed is 25 amp
ELE14-00212 Final12/10/201412/11/201412/11/2014 1:36:13 PMPPASS
Please call the homeowner Amy ###-#### for access and please call Clay to meet you there ###-####. Thank You!!!! Phone #: ###-#### Inspection requested via web by Clay Morgan
corrections made, final OK
ELE14-02767 Final12/11/201412/11/201412/11/2014 1:05:44 PMPFAIL
Phone #: ###-#### Inspection requested via web by Lars Johnson
called Lars
210.8.7. GFI protection required within 6 foot from edge of sinks
422.31 DIsxonnecting means required for fixed appliances, furnace
334.15 NM cable shall be protected from physical damage, furnace
ELE14-03403 Final12/10/201412/11/201412/11/2014 12:21:32 PMANH
wire gas fireplace Phone #: ###-#### Inspection requested via web by PAT MILLER
no access, called pat
ELE14-03403 Electrical Rough-In12/10/201412/11/201412/11/2014 12:21:31 PMANH
Phone #: ###-#### Inspection requested via web by PAT MILLER
no access, called pat
ELE14-03125 Final12/10/201412/11/201412/11/2014 9:54:57 AMAPASS
code is 2468 on garage. thanks Phone #: ###-#### Inspection requested via web by Darryn Coburn
FInal OK
ELE12-01040 Final12/10/201412/11/201412/11/2014 9:26:10 AMAPASS
Donald Phone #: ###-####
final ok
ELE13-03535 Final12/8/201412/11/201412/11/2014 9:10:01 AMAFAIL
Phone #: 2088661213 >> Inspection requested via mobile web by Todd Nelson
spoke with owner about corrections
romex must be secured within 12 inches of box
permanently attached appliances shall have means of disconnect, ovens, d/w, rangehood, micro
romex shall be subject to damage, provide cover
ELE14-03081 Final12/10/201412/11/201412/11/2014 8:32:34 AMAPASS
Phone #: ###-#### Inspection requested via web by David Seilheimer
corrections made, final OK
ELE14-03411 Final12/10/201412/11/201412/11/2014 8:14:49 AMAPASS
David-ask for Shelley Phone #: ###-####
see rough inspection
ELE14-03411 Electrical Rough-In12/10/201412/11/201412/11/2014 8:14:23 AMAPASS
David Phone #: ###-####-ask fopr Shelley
UL listed non-ballsted LED lamps, RI OK