Inspections for the day of: Friday, December 11, 2015.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-00137 FIRE-Final Inspection12/11/201512/11/201512/11/2015 4:21:09 PMPPART
Fire sprinkler inspection complete, fire alarm inspection complete. Life fire safety inspection peformed, only item not in place for inspection is the emergency exit discharge light located in the west canopy, all other items inspected/passed, will final life fire safety when emergency egress light is installed/operational.
BLD15-02075 FIRE-Final Inspection12/11/201512/11/201512/11/2015 4:15:53 PMPPASS
No fire sprinklers, fire alarm inspection complete. Life fire safety inspection passed/complete. The northwest door of tenant space (kitchen/dishwasher area) has thumb-turn deadblot on door, instructed to the superintendant of jod that the thumb turn will need to be changed to double key assembly or removed, he instructed to me that the thumb-turn was keyed for construction access and that the thumb-turn will be removed at completion of project.
FIR15-00722 INSP-Final Inspection12/11/201512/11/201512/11/2015 4:11:35 PMPPASS
Final fire alarm inspection passed/complete
FIR15-00722 INSP-Sprinkler Rough-in/Hydro12/9/201512/11/201512/11/2015 4:10:06 PMACANC
Inspection request for fire alarm final, canceling this inspection and correcting inspection request
FIR15-00601 INSP-Final Inspection12/11/201512/11/201512/11/2015 3:48:13 PMPPASS
All previously noted items repaired. Final fire sprinkler inspection passed/complete.
BLD15-03145 FIRE-Final Inspection12/10/201512/11/201512/11/2015 2:03:48 PMPFAIL
Exit signs/lights must be illimunated at all times under normal building power. Exit signs/lights also need to have an emergency power supply able to provide not less than 90 minutes of power. Emergency egress lighting needs to be installed on the second level, currently the only emergency lighting on the floor is in the restrooms.
FIR15-00843 INSP-Sprinkler Rough-in/Hydro12/10/201512/11/201512/11/2015 8:38:11 AMAPASS
Rough to cover inspection for tenant space passed/complete, approved for cover.
FIR14-00751 INSP-Final Inspection12/10/201512/11/201512/10/2015 4:10:33 PMPCANC
Bldg L Final and trip test Please call Raul 30 min prior ###-#### Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
FIR14-00751 INSP-Final Inspection12/10/201512/11/201512/10/2015 4:08:18 PMPCANC
Bldg L Final and trip test
Please call Raul 30 min prior ###-#### Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
FIR14-00071 INSP-Final Inspection12/10/201512/11/201512/10/2015 4:08:16 PMPCANC
Bldg L Final and trip test
Please call Raul 30 min prior ###-#### Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt