Inspections for the day of: Monday, December 11, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03390 Final12/11/201712/11/201712/11/2017 2:39:58 PMPFAIL
Mitch Phone #: ###-####
110.3- GFCI in garage opposite wall from panel shows open ground.
110.27- All wiring in unfinished garage walls located below 8' shall be protected from physical damage. Ceiling not 8' so cover wiring up to ceiling in stud bays where exposed.
210.8- GFCI devices shall be located in a readily accessible areas. Eave receptacle located above 6'7".
ELE17-03410 Final12/11/201712/11/201712/11/2017 2:03:08 PMPPASS
Garage code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
ELE17-03012 Final12/9/201712/11/201712/11/2017 1:20:34 PMAPASS
Dispenser and tank monitor wiring. Phone #: ###-#### Inspection requested via web by Paul White
Final ok
ELE17-03012 Electrical Rough-In12/11/201712/11/201712/11/2017 1:19:34 PMPPASS
Dispenser and tank monitor wiring. Phone #: ###-#### Inspection requested via web by Paul White
All conduits installed by others. This permit covers wiring, sealing, and functioning pumps, tanks emergency systems. Rough in ok cover
ELE17-02787 Final12/8/201712/11/201712/11/2017 12:54:22 PMANH
Please call Eric ###-#### for access Phone #: ###-#### Inspection requested via web by Emmet Bushman
Called contact number for access and reached and voicemail for Mike not Eric. Called contractor and he was unable to reach contact. Will reschedule
ELE17-03548 Final12/11/201712/11/201712/11/2017 10:21:38 AMAFAIL
Phone #: ###-#### Inspection requested via web by Kevin Perez .
210.12- AFCI protection needed for circuit extension in basement bedroom. Thru door receptacles to right.
314.20- Spark ring needed on basement column to left or box shall be flush.
422.30- A disconnecting means shall be provide for hardwired appliances. 110.15 lockout acceptable.
ELE17-03513 Electrical Rough-In12/10/201712/11/201712/11/2017 9:30:31 AMAPASS
Heated tile floor inspection in bathrooms Phone #: ###-#### Inspection requested via web by Ben Archibald
Floor heat 2 bathrooms rough in ok cover
ELE17-04136 Temporary Service12/8/201712/11/201712/11/2017 9:18:54 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE17-04135 Temporary Service12/8/201712/11/201712/11/2017 9:18:29 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE17-04141 Electrical Rough-In12/10/201712/11/201712/11/2017 8:47:12 AMAPASS
Phone #: ###-#### Inspection requested via web by Brad Girard
Entry wall on right, down hall to left for wall near printing area. wall rough in ok cover
ELE17-04028 Electrical Rough-In12/8/201712/11/201712/9/2017 9:51:01 AMACANC
As early as possible would be appreciated. Phone #: ###-#### >> Inspection requested via web by Matt Frey Inspection cancelled from web by: Matt Frey