Inspections for the day of: Monday, December 12, 2005.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04464 Final12/12/200512/12/200512/12/2005 3:40:44 PMPNR
clyde ###-####//call for access
no power to check outlets
ELE05-03326 ELE-Aging Inspection12/12/200512/12/200512/12/2005 2:47:13 PM NR
no sign there
ELE05-04074 Conference12/12/200512/12/200512/12/2005 2:39:17 PMPPART
mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
ELE05-04464 Permanent Service12/12/200512/12/200512/12/2005 2:13:12 PMPPASS
clyde ###-####
P/S O/H N Ok
ELE05-00944 ELE-Aging Inspection12/12/200512/12/200512/12/2005 1:52:47 PM NR
called contractor is checking if finished yet
ELE05-04084 Final12/12/200512/12/200512/12/2005 1:50:31 PMPNR
call 1st before insp -kevin ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
had conf and walkthrough still some strapping in ceiling and 1 room no grid yet
ELE05-04435 Electrical Rough-In12/12/200512/12/200512/12/2005 1:49:25 PMPPART
call 1st before insp -kevin ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
all ok except a small section of ceiling by the door.
ELE05-04447 Temporary Service12/12/200512/12/200512/12/2005 12:57:04 PMPPASS
Scheduled by a contractor via Hello! on 12/12/2005 at 9:30:35 AM. Contact: ###-####.
T/S U/g Ok
ELE05-00786 ELE-Aging Inspection12/12/200512/12/200512/12/2005 12:35:28 PM NR
no work done
ELE04-03874 Final12/9/200512/12/200512/12/2005 12:20:47 PMAFAIL
Phone #: ###-#### Internet Inspection Request from: Heather Packer
posted correction with 5 days time limit.
ELE05-00882 Electrical Rough-In12/9/200512/12/200512/12/2005 11:31:17 AMANR
brian; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
mast not supported cannot locate water bonding/grounding
210.52
connector required
access to box below panel
undersize boxes
ground slb
ELE05-03193 Electrical Rough-In12/9/200512/12/200512/12/2005 10:50:52 AMANR
Phone #: ###-#### Internet Inspection Request from: Tina Payne
partial R/I OK
nurse call shower area and kitchen ok
ELE05-04377 Rough-In Permanent Service12/12/200512/12/200512/12/2005 10:16:18 AMAFAIL
Scheduled by a contractor via Hello! on 12/12/2005 at 6:38:14 AM. Contact: ###-####.
service has no connector on grounding electrode conductor
use proper connectors on se cable
install main
disconnect and grounding on house
bending radius to short on se cable
ELE05-04394 Final12/11/200512/12/200512/12/2005 9:28:53 AMAFAIL
call Charlie--key under mat Internet Inspection Request from: Melyne Davis
derate wires
screws in nm boxes
service drop too low
bond hot water
directory not clear
ELE05-04457 Permanent Service12/9/200512/12/200512/12/2005 8:19:18 AMAPASS
tim ###-####
P/S U/G N Ok