FIR05-00648
| INSP-Sprinkler Rough-in/Hydro | 12/12/2005 | 12/12/2005 | 12/13/2005 1:57:00 PM | P | PASS |
|
|
Sprinkler piping is ok to cover. Corrections made.
|
BLD05-02868
| FIRE-Final Inspection | 12/12/2005 | 12/12/2005 | 12/12/2005 4:06:43 PM | P | PASS |
|
|
Life safety finaled
|
BLD05-01388
| FIRE-Final Inspection | 12/9/2005 | 12/12/2005 | 12/12/2005 12:49:54 PM | A | PASS |
|
|
Fire life safety passed
|
FIR05-00312
| INSP-Sprinkler Rough-in | 12/9/2005 | 12/12/2005 | 12/12/2005 10:46:59 AM | A | FAIL |
|
|
No inspection is supposed to be called in but I did it anyway. Alot of changes have taken place with the piping. Per fitter these changes are reflected on another resubmittal that is in for review. This includes heads repiped and added in the second floor dry remote area, branchline added on the lower level dry system and main reroutes. Dry system heads dont meet 8.6.5.2.1.6 for spacing.
|
BLD05-02869
| FIRE-Final Inspection | 12/9/2005 | 12/12/2005 | 12/12/2005 10:39:45 AM | A | PASS |
|
|
fire life safety finaled. The 2a10bc fire extinguisher is on its way. Dead bolts have been removed for the second time from office doors.
|