Inspections for the day of: Monday, December 12, 2005.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00648 INSP-Sprinkler Rough-in/Hydro12/12/200512/12/200512/13/2005 1:57:00 PMPPASS
Sprinkler piping is ok to cover. Corrections made.
BLD05-02868 FIRE-Final Inspection12/12/200512/12/200512/12/2005 4:06:43 PMPPASS
Life safety finaled
BLD05-01388 FIRE-Final Inspection12/9/200512/12/200512/12/2005 12:49:54 PMAPASS
Fire life safety passed
FIR05-00312 INSP-Sprinkler Rough-in12/9/200512/12/200512/12/2005 10:46:59 AMAFAIL
No inspection is supposed to be called in but I did it anyway. Alot of changes have taken place with the piping. Per fitter these changes are reflected on another resubmittal that is in for review. This includes heads repiped and added in the second floor dry remote area, branchline added on the lower level dry system and main reroutes. Dry system heads dont meet 8.6.5.2.1.6 for spacing.
BLD05-02869 FIRE-Final Inspection12/9/200512/12/200512/12/2005 10:39:45 AMAPASS
fire life safety finaled. The 2a10bc fire extinguisher is on its way. Dead bolts have been removed for the second time from office doors.