Inspections for the day of: Tuesday, December 12, 2006.
Number of inspections: 24
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-03298 FIRE-Final Inspection12/12/200612/12/200612/12/2006 5:02:05 PMPPASS
Life safety finaled
FIR06-00839 INSP-Final Inspection12/12/200612/12/200612/12/2006 4:59:02 PMPPASS
Permit finaled
FIR06-00259 INSP-Final Inspection12/12/200612/12/200612/12/2006 4:58:20 PMPPASS
Permit finaled
FIR06-00543 INSP-Final Inspection12/12/200612/12/200612/12/2006 4:58:04 PMPPASS
Permit finaled
BLD06-00169 FIRE-Final Inspection12/12/200612/12/200612/12/2006 3:46:18 PMPFAIL
Provide pavement, provide fire lane signage per sheet A1-1a, provide sticker at the main exit, provide remote annunciator and test the duct smoke detector and provide the fire dept. review comments for other possible requirements.
FIR06-00789 INSP-Sprinkler Rough-in/Hydro12/8/200612/12/200612/12/2006 3:41:15 PMPFAIL
No approved overhead sprinkler plans on site. No inspection performed.
FIR06-00098 INSP-Final Inspection12/12/200612/12/200612/12/2006 3:25:43 PMPPASS
permit finaled
BLD05-03243 FIRE-Alarm Testing12/12/200612/12/200612/12/2006 3:07:24 PMPPASS
Life safety finaled
FIR06-00722 INSP-Final Inspection12/12/200612/12/200612/12/2006 3:03:50 PMPFAIL
Need to test the interconnection with the alarm system.
FIR06-00628 INSP-Final Inspection12/12/200612/12/200612/12/2006 3:02:33 PMPPASS
Underground permit finaled
FIR06-00750 INSP-Final Inspection12/11/200612/12/200612/12/2006 2:01:53 PMPFAIL
No test performed since a supervisory signal from an unknown source was showing. The electricians where working on it as I left. No inspection performed.
BLD06-01554 FIRE-Final Inspection12/11/200612/12/200612/12/2006 1:59:21 PMAFAIL
Life safety items will be ok to final when the fire alarm permit is finaled
BLD06-02317 FIRE-Final Inspection12/11/200612/12/200612/12/2006 1:49:43 PMAFAIL
Need to repair the two emergency lights, the access controled egress door does not meet IFC chapter 10 and the second fire extinguisher for the warehouse needs to be hung
BLD06-00051 FIRE-Final Inspection12/11/200612/12/200612/12/2006 1:25:52 PMAPASS
Life safety for the building shell is passed.
FIR05-00536 INSP-Sprinkler Rough-in12/12/200612/12/200612/12/2006 12:51:20 PMPPASS
Pendants located in the soffets in auditorium are ok to cover.
FIR06-00909 INSP-Final Inspection12/11/200612/12/200612/12/2006 11:00:13 AMAPASS
Permit finaled.
BLD06-01569 FIRE-Final Inspection12/11/200612/12/200612/12/2006 10:59:48 AMAFAIL
The fire alarm permit for these projects needs applied for. Peak Alarm has demo'd notification devices when the construction work was being performed per Bill with Peak. I have notified Mike Timmerman about the situation. Bill stated he would call Mike Timmerman to find out what needs to be done.
BLD06-01568 FIRE-Final Inspection12/11/200612/12/200612/12/2006 10:59:33 AMAFAIL
The fire alarm permit for these projects needs applied for. Peak Alarm has demo'd notification devices when the construction work was being performed per Bill with Peak. I have notified Mike Timmerman about the situation. Bill stated he would call Mike Timmerman to find out what needs to be done.
BLD06-01567 FIRE-Final Inspection12/11/200612/12/200612/12/2006 10:59:18 AMAFAIL
The fire alarm permit for these projects needs applied for. Peak Alarm has demo'd notification devices when the construction work was being performed per Bill with Peak. I have notified Mike Timmerman about the situation. Bill stated he would call Mike Timmerman to find out what needs to be done.
BLD06-01566 FIRE-Final Inspection12/11/200612/12/200612/12/2006 10:59:04 AMAFAIL
The fire alarm permit for these projects needs applied for. Peak Alarm has demo'd notification devices when the construction work was being performed per Bill with Peak. I have notified Mike Timmerman about the situation. Bill stated he would call Mike Timmerman to find out what needs to be done.
FIR06-00577 INSP-Final Inspection12/12/200612/12/200612/12/2006 10:56:11 AMPPASS
Permit finaled
BLD05-02436 FIRE-Final Inspection12/11/200612/12/200612/12/2006 8:32:46 AMAPASS
Permit finaled
FIR06-00499 FIR-Aging Inspection12/12/200612/12/200612/12/2006 8:26:29 AM NR
Work in progress
BLD06-01173 FIRE-Final Inspection12/11/200612/12/200612/11/2006 10:43:01 AMACANC
Phone #: ###-#### Internet Inspection Request from: Todd Kurns Inspection cancelled from web by: Todd Kurns