Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03176 ELE-Aging Inspection12/12/200712/12/200712/13/2007 2:45:34 PM DONE
see final
ELE07-04078 Temporary Service12/11/200712/12/200712/13/2007 11:49:01 AMAPASS
TEMP POLE INSTALLED AND READY FOR INSPECTION Phone #: ###-#### Internet Inspection Request from: BRENDA HURST called, left survey, nec 350.30(A) flexible conduit shall be strapped within 12" of box, 110.12(C) there shall be no broken parts( receptacle cover) t/s o/h n ok
ELE07-03174 ELE-Aging Inspection12/12/200712/12/200712/12/2007 4:10:39 PM DONE
see final
ELE07-03174 Final12/12/200712/12/200712/12/2007 3:55:03 PMPPASS
looked at sign, ok to final
ELE07-00745 Electrical Rough-In12/12/200712/12/200712/12/2007 3:49:32 PMPFAIL
david Phone #: ###-#### met owner, left correction notice, BCC all make-up shall be done,NEC 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing member, 314.17(C) nm cable shall be stapled within 8" of box, 314.20 box shall be flush with finished surface of combustible material, 250.148(C) shall ground metal box
ELE07-04103 Electrical Rough-In12/12/200712/12/200712/12/2007 2:37:35 PMPPASS
mike Phone #: ###-#### ric ok house and garage, no service or u/g ready to inspect
ELE07-03650 Final12/12/200712/12/200712/12/2007 1:39:56 PMPPASS
glenn Phone #: ###-#### ok to final, no card to sign
ELE07-03958 Permanent Service12/12/200712/12/200712/12/2007 12:49:58 PMPCANC
rocky-- ###-#### see conference
ELE07-03958 Conference12/12/200712/12/200712/12/2007 12:49:43 PMPDONE
rocky-- ###-#### met electrician, discussed warm walls and concrete encased electrode for new construction
ELE07-03114 Final12/11/200712/12/200712/12/2007 10:45:29 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton ok to final, signed occupancy card
ELE07-03789 Electrical Rough-In12/12/200712/12/200712/12/2007 10:00:35 AMPPASS
corrections made garage only, ric ok- house needs 6" free conductor 2 places in kitchen, nail plate, strap nm cable over panel, code references in garage on correction notice that 370 left
ELE07-03448 Final12/11/200712/12/200712/12/2007 9:56:33 AMAPASS
Scheduled by a contractor via Hello! on 12/11/2007 at 7:54:12 PM. Contact: ###-####. ok to final
ELE07-01624 Electrical Rough-In12/11/200712/12/200712/12/2007 8:36:16 AMAPASS
Carl Phone #: ###-#### ok to cover rest of dropped in ceiling anop