Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-01568 Final12/12/200812/12/200812/12/2008 2:39:24 PMPPASS
Scheduled by a contractor via Hello! on 12/12/2008 at 8:20:27 AM. Contact: ###-####. ok card signed
ELE08-03090 Electrical Rough-In12/12/200812/12/200812/12/2008 2:39:00 PMPPART
Underground Building C Phone #: ###-#### Internet Inspection Request from: Celinda Winters u/g ok
ELE08-03223 Electrical Rough-In12/12/200812/12/200812/12/2008 1:38:58 PMPPART
Underground inspection. Contact is Nick his no. is ###-#### Phone #: ###-#### Internet Inspection Request from: Shawna Gates u/g for sign N W corner
ELE08-03023 Electrical Rough-In12/12/200812/12/200812/12/2008 12:23:11 PMPPART
Please provide underground flat work inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean u/g for 4 floor boxes ok
ELE08-03186 Final12/11/200812/12/200812/12/2008 10:41:50 AMAPASS
stu Phone #: ###-#### ok
ELE08-02182 Permanent Service12/11/200812/12/200812/12/2008 9:58:57 AMPFAIL
Bud Horsley is contact Phone #: ###-#### Internet Inspection Request from: Cyndi Dale met contr GEC shall terminate to neutral without splice, and remove load conductors from CT can
ELE08-03220 Electrical Rough-In12/11/200812/12/200812/12/2008 9:22:40 AMAFAIL
jeremy Phone #: ###-#### wiring not done to plans on site house wired for 2 kitchens call plan check house con only have 1 kitchen contr will remove range circuit
ELE08-03216 Electrical Rough-In12/11/200812/12/200812/12/2008 9:17:23 AMACANC
Glen Phone #: ###-#### contr. called and canceled
ELE08-03219 Rough-In Permanent Service12/11/200812/12/200812/12/2008 8:23:03 AMAPASS
tom Phone #: ###-#### r/i p/s u/g new ok
ELE08-03219 Final12/12/200812/12/200812/12/2008 8:22:42 AMAPASS
tom Phone #: ###-####