Inspections for the day of: Monday, December 12, 2011.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00604 INSP-Alarm Testing12/9/201112/12/201112/12/2011 4:00:32 PMPCANC
Cancelled due to time constraints.
FIR11-00263 INSP-Final Inspection12/12/201112/12/201112/12/2011 3:58:46 PMPFAIL
Provide strobe modifications as discussed to provide coverage in the deficient areas. All of the strobes in the shop areas are mounted too high. The need to meet NFPA 72 mounting heights, go with the performance based design (lighting calculations) or take it up with the fire marshal. As-builts need to be provided showing the strobe modifications and one additional pull station. This is to include revised one line and EOL calculations. Signals were sent out on phone line #1 but not phone line #2 so that needs to be tested as well. We discussed the phone lines as possibly be ground start and not loop start as required per NFPA 72 26.6.3.2.1.1. When the contractor calls my phone the same number comes up and he must dial "9" first.
FIR11-00401 INSP-Final Inspection12/8/201112/12/201112/12/2011 9:55:58 AMAPASS
Permit finaled.
BLD11-01171 FIRE-Final Inspection12/9/201112/12/201112/12/2011 8:48:04 AMAFAIL
Jenean Phone #: ###-#### I left a message on the contacts voice mail and drove to the job site where I found two locked doors and no access. No inspection was performed.