BLD12-03072
| FIRE-Final Inspection | 12/12/2012 | 12/12/2012 | 12/19/2012 7:39:19 AM | P | FAIL |
|
|
Provide min. 2A10BC rated fire extinguishers within allowable travel distances per floor level as discussed.
|
BLD12-03071
| FIRE-Final Inspection | 12/12/2012 | 12/12/2012 | 12/19/2012 7:38:50 AM | P | FAIL |
|
|
Provide min. 2A10BC rated fire extinguishers within allowable travel distances per floor level as discussed.
|
BLD12-01941
| FIRE-Final Inspection | 12/12/2012 | 12/12/2012 | 12/12/2012 3:12:09 PM | P | PASS |
|
|
Fire life safety final approved.
|
FIR12-00652
| INSP-Final Inspection | 12/12/2012 | 12/12/2012 | 12/12/2012 3:08:16 PM | P | PASS |
|
|
Fire alarm work passed functional testing. Permit finaled.
|
FIR12-00654
| INSP-Final Inspection | 12/11/2012 | 12/12/2012 | 12/12/2012 3:07:04 PM | A | PART |
|
|
Hood suppression system operated correctly under test conditions. Permit final pending design submittal matching the field installation and kitchen equipment layout.
|
BLD12-02498
| FIRE-Final Inspection | 12/11/2012 | 12/12/2012 | 12/12/2012 3:03:40 PM | A | FAIL |
|
|
Items noted include; provide approved plans and permit documents on site, fire extinguishers are overdue annual certification, remove tape and paper covering the duct detectors.
|