BLD14-00819
| FIRE-Final Inspection | 12/11/2014 | 12/12/2014 | 12/12/2014 3:43:54 PM | P | PASS |
|
|
Fire life safety passed
|
BLD14-02475
| FIRE-Final Inspection | 12/11/2014 | 12/12/2014 | 12/12/2014 3:43:07 PM | P | PASS |
|
|
Fire life safety passed
|
FIR14-00699
| INSP-Final Inspection | 12/12/2014 | 12/12/2014 | 12/12/2014 3:42:44 PM | P | PASS |
|
|
Permit finaled
|
BLD14-03511
| FIRE-Final Inspection | 12/11/2014 | 12/12/2014 | 12/12/2014 3:37:00 PM | P | CANC |
|
|
Overbooked.. Rescheduled for monday.
|
BLD14-03518
| FIRE-Final Inspection | 12/12/2014 | 12/12/2014 | 12/12/2014 3:26:52 PM | P | CANC |
|
|
Overbooked rescheduled for Monday
|
FIR14-00691
| INSP-Final Inspection | 12/11/2014 | 12/12/2014 | 12/12/2014 3:18:22 PM | P | FAIL |
|
|
Need to show additional tamper valve on the anti-freeze loop, duct detectors in Harbor Freight did not shut down the hvac units and a separate but some what interconnected fire alarm system in the Buffalo Club. I need John to find out the exact sequence of operation of both panels and how they are interconnected and extent of the fire sprinkler system that the two panel cover and present this information to plan review for a plan modification.
|
FIR14-00689
| INSP-Final Inspection | 12/11/2014 | 12/12/2014 | 12/12/2014 3:04:42 PM | P | FAIL |
|
|
Was only able to verify netcon, PIV and wet system flow switch. Duct smoke detectors were not connected to thermostats so that they could be turned on. Need to test dry system devices and hoods in the Chinese Restraunt.
|
BLD14-02066
| FIRE-Final Inspection | 12/12/2014 | 12/12/2014 | 12/12/2014 11:43:27 AM | P | PASS |
|
|
Life safety passed
|
BLD14-02095
| FIRE-Final Inspection | 12/12/2014 | 12/12/2014 | 12/12/2014 11:38:13 AM | P | PASS |
|
|
life safety passed
|
FIR14-00721
| INSP-Final Inspection | 12/12/2014 | 12/12/2014 | 12/12/2014 11:36:43 AM | P | PASS |
|
|
permit finaled and underground flush passed
|
BLD13-03185
| FIRE-Conference | 12/12/2014 | 12/12/2014 | 12/12/2014 10:35:09 AM | P | DONE |
|
|
Discussed address placement
|
FIR14-00581
| INSP-Final Inspection | 12/11/2014 | 12/12/2014 | 12/12/2014 10:27:34 AM | A | PASS |
|
|
permit finaled
|
BLD14-01510
| FIRE-Final Inspection | 12/12/2014 | 12/12/2014 | 12/12/2014 10:24:50 AM | P | PASS |
|
|
Life safety passed
|
BLD14-02878
| FIRE-Final Inspection | 12/12/2014 | 12/12/2014 | 12/12/2014 10:21:01 AM | P | PART |
|
|
A temporary occupancy is being given with scotts's approval until Alarmco provides permit and testing of the duct smoke detector
|
FIR14-00820
| INSP-Final Inspection | 12/11/2014 | 12/12/2014 | 12/12/2014 10:12:45 AM | A | PASS |
|
|
permit finaled
|
FIR14-00495
| INSP-Final Inspection | 12/12/2014 | 12/12/2014 | 12/12/2014 10:00:01 AM | P | PASS |
|
|
Permit finaled
|
BLD14-03086
| FIRE-Final Inspection | 12/11/2014 | 12/12/2014 | 12/12/2014 9:57:45 AM | A | PART |
|
|
A temporary occupancy is being given with scott's permission until the fire alrm is extended into this tenant space as per upgrade agreement. See FIR03-00803
|
FIR14-00852
| INSP-Final Inspection | 12/11/2014 | 12/12/2014 | 12/12/2014 9:06:52 AM | A | PASS |
|
|
Permit finaled
|