FIR18-00428
| INSP-Final Inspection | 12/11/2018 | 12/12/2018 | 12/12/2018 3:11:22 PM | A | FAIL |
|
|
Need all ceiling tile installed prior to a final for the 3rd floor.
Tony Cetani is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-02834
| FIRE-Final Inspection | 12/12/2018 | 12/12/2018 | 12/12/2018 2:33:51 PM | P | FAIL |
|
|
Life safety will be ok to pass when I'm directed by the Building Dept/Fire Dept. that an acceptable agreement has been reached on the fire sprinkler system.
|
FIR18-00879
| INSP-Final Inspection | 12/12/2018 | 12/12/2018 | 12/12/2018 2:32:48 PM | P | PASS |
|
|
Permit finaled
|
FIR18-00776
| INSP-Supply line flush | 12/11/2018 | 12/12/2018 | 12/12/2018 1:54:09 PM | P | PASS |
|
|
Underground flush passed. Flow was not as expected so Suez is going to follow up that the flow is as provided for design.
Set up for 1:00 pm Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR18-00775
| INSP-Supply line flush | 12/11/2018 | 12/12/2018 | 12/12/2018 1:53:33 PM | P | PASS |
|
|
Underground flush passed. Flow was not as expected so Suez is going to follow up that the flow is as provided for design.
Set up for 1:00 pm Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD18-03617
| FIRE-Final Inspection | 12/12/2018 | 12/12/2018 | 12/12/2018 1:27:04 PM | P | PASS |
|
|
Life safety passed. Matt to install lever hardware on the east side door as per plan prior to a building inspection.
Matt Phone #: ###-####
|
BLD18-04295
| FIRE-Final Inspection | 12/11/2018 | 12/12/2018 | 12/12/2018 12:06:35 PM | P | PASS |
|
|
Life safety passed
Keith Phone #: ###-####
|
BLD18-03509
| FIRE-Final Inspection | 12/12/2018 | 12/12/2018 | 12/12/2018 11:45:40 AM | P | PASS |
|
|
life safety passed
Call half hour before to meet // Tim Phone #: ###-####
|
FIR18-00903
| INSP-Final Inspection | 12/11/2018 | 12/12/2018 | 12/12/2018 10:53:10 AM | A | FAIL |
|
|
Scope of work is complete but permit can not be finaled until the fire sprinkler system monitoring system has been installed and tested.
Adam Phone #: ###-####
|
FIR18-00583
| INSP-Sprinkler Rough-in | 12/11/2018 | 12/12/2018 | 12/12/2018 9:28:15 AM | A | FAIL |
|
|
This inspection was for the Area "C" Fitness Center. Piping could not be viewed due to insulation blocking it. Could not perform inspection. No piping to be covered prior to a rough-in inspection.
Tony Cetani is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00708
| INSP-Sprinkler Rough-in | 12/11/2018 | 12/12/2018 | 12/12/2018 9:26:54 AM | A | PASS |
|
|
The piping above the hardlids in Area "C" Restrooms at the east side of the building is ok for cover.
Tony Cetani is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|