Inspections for the day of: Thursday, December 13, 2001.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR01-00510 INSP-Sprinkler Rough-in12/12/200112/13/200112/14/2001 12:00:00 AMAFAIL
###-#### c/n issued: standpipe submittals required; 3/4 inch lines used to feed under stairs on third floor require calc's; 4 inch main in basement needed per calcs 12/14/2001 11:11:41 AM
FIR01-00474 INSP-Final Inspection12/12/200112/13/200112/13/2001 12:00:00 AMAFAIL
###-#### c/n issued 12/13/2001 4:44:46 PM
FIR01-00344 INSP-Alarm Testing12/12/200112/13/200112/13/2001 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 12/12/2001 at 12:22:12. Contact: ###-####. c/n issued 12/13/2001 11:18:00 AM
BLD01-00534 FIRE-Final Inspection12/12/200112/13/200112/13/2001 12:00:00 AMANR
Scheduled by a contractor via Hello! on 12/12/2001 at 16:08:23. Contact: ###-####.
FIR01-00442 INSP-Supply line flush12/12/200112/13/200112/13/2001 12:00:00 AMAPASS
###-#### MIKE
FIR01-00305 INSP-Final Inspection12/13/200112/13/200112/13/2001 12:00:00 AMPPASS
Added by Inspector: 409 On 12/13/2001 4:38:15 PM
BLD01-01345 FIRE-Final Inspection12/13/200112/13/200112/13/2001 12:00:00 AMPFAIL
Added by Inspector: 409 On 12/13/2001 4:44:31 PM sprinklers in concealed combustible spaces or cover; c/n issued
BLD99-03148 FIRE-Conference12/14/200112/13/200112/13/2001 12:00:00 AMPPART
Added by Inspector: 409 On 12/14/2001 1:56:24 PM met with Brett after a report of the FACP was in a trouble condition. room 210 has a wiring problem. issued a correction notice to have the item repaired. follow up inspection on 12/14