Inspections for the day of: Thursday, December 13, 2001.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD01-00754 FIRE-Final Inspection12/12/200112/13/200112/13/2001 12:00:00 AMAPASS
Fire life/safety finaled 12/13/2001 10:53:32 AM
BLD01-02603 FIRE-Final Inspection12/12/200112/13/200112/13/2001 12:00:00 AMAPASS
Fire life/safety finaled 12/13/2001 10:16:59 AM
BLD01-00265 FIRE-Final Inspection12/12/200112/13/200112/13/2001 12:00:00 AMAPASS
fire life/safety finaled 12/13/2001 7:42:08 AM
FIR01-00541 INSP-Final Inspection12/11/200112/13/200112/13/2001 12:00:00 AMAPASS
Fire alarm system finaled 12/13/2001 9:50:57 AM
FIR01-00601 INSP-Final Inspection12/13/200112/13/200112/13/2001 12:00:00 AMAPASS
Added by Inspector: 430 On 12/13/2001 10:15:53 AM FIre sprinkler system finaled
FIR01-00330 INSP-Final Inspection12/12/200112/13/200112/13/2001 12:00:00 AMPFAIL
provide additional D113 module for battery supervision and test batteries, adjust tamper switch on gate valve to give steady signal, provide tamper switch on alarm valve trim, adjust flow switch so alarm comes in under 90 seconds, provide map of system at fire alarm panel, provide NFPA 72 forms 12/13/2001 12:38:35 PM
MIS01-00216 FIR-Final12/12/200112/13/200112/13/2001 12:00:00 AMPPASS
Fire life/safety finaled 12/13/2001 2:20:58 PM
BLD01-01483 FIRE-Final Inspection12/13/200112/13/200112/13/2001 12:00:00 AMPPASS
Fire life/safety finaled 12/13/2001 1:53:38 PM