Inspections for the day of: Friday, December 13, 2002.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-00001 BLD-Aging Inspection12/13/200212/13/200212/13/2002 12:00:00 AM NR
I spoke with the head maintenance person named Ted and discussed what was needed for them to get their final inspection. There were no city approved plans on site. Sprinkler work will need to be performed due to heads blocked by new equipment. 12/16/2002 9:47:32 AM
FIR01-00613 FIR-Aging Inspection12/13/200212/13/200212/13/2002 12:00:00 AM NR
I spoke to the fire alarm contractor and they are going to follow up with the architect to get the final inspection taken care of 12/13/2002 3:54:37 PM
FIR02-00456 INSP-Final Inspection12/13/200212/13/200212/13/2002 12:00:00 AMAFAIL
missing canopies on the sprinkler pendants and the sprinkler heads in the file room are overspaced for ordinary hazard
BLD02-00311 FIRE-Final Inspection12/12/200212/13/200212/13/2002 12:00:00 AMAPART
see the city approved fire alarm plans for the areas that are dated with todays date that are ok to occupy for this phase of the project 12/13/2002 8:27:02 AM
FIR02-00239 INSP-Final Inspection12/12/200212/13/200212/13/2002 12:00:00 AMAPASS
TERESA ###-####
FIR02-00405 INSP-Sprinkler Rough-in12/12/200212/13/200212/13/2002 12:00:00 AMAPART
hard lid areas are ok to cover. Sprinkler heads need to be added over the egress corridor and the other rooms where there are no uprights. This is in locations where there is not a tenant on either side of these rooms. I spoke to Greg at Treasure Valley Fire about this. A sprinkler head needs to be added under the 2nd floor stairs 12/13/2002 1:23:59 PM
BLD02-02321 FIRE-Conference12/12/200212/13/200212/13/2002 12:00:00 AMADONE
I spoke with the contractor and the electrical contractor about the placement for the duct smoke detectors and electrical shutoff under the type 1 hood 12/13/2002 9:40:40 AM
BLD02-02303 FIRE-Final Inspection12/12/200212/13/200212/13/2002 12:00:00 AMAFAIL
verify that the existing fire alarm monitoring panel meets current code or provide city approved drawings and a upgraded system, sprinkler heads in the file room are space per light hazard. They must be spaced for ordinary hazard. 12/13/2002 11:08:59 AM
BLD01-02828 FIRE-Final Inspection12/13/200212/13/200212/13/2002 12:00:00 AMPPASS
fire alarm finaled
FIR02-00332 INSP-Alarm Testing12/11/200212/13/200212/11/2002 4:24:28 PMPCANC
Troy, If you could call me and let me know as far in advance when you will be able to make it out to Emser Tile on Friday I would appreciate it. My cell number is ###-####, and the office is ###-####.
Thanks,
Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick