Inspections for the day of: Monday, December 13, 2004.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00599 INSP-Final Inspection12/10/200412/13/200412/13/2004 12:13:35 PMPCANC
This is Grants cell. Have a great weekend!!; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
FIR04-00612 INSP-Final Inspection12/13/200412/13/200412/13/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 12/13/2004 at 7:42:10 AM. Contact: ###-####. The 1.5 inch was shifted to the south due to lights and has armovers for the heads in the storage area and the line shifts back to the center above the cooler 12/13/2004 1:35:45 PM
FIR04-00710 INSP-Alarm Testing12/13/200412/13/200412/13/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 12/13/2004 at 8:37:24 AM. Contact: ###-####. Need detectors in beam pockets - beams are 18 inches deep; resubmittals required per Mary 12/13/2004 4:30:03 PM
MIS04-00332 FIR-Final12/13/200412/13/200412/13/2004 12:00:00 AMPFAIL
Extinguisher overdue certification; suite numbers 12/13/2004 2:15:59 PM