Inspections for the day of: Monday, December 13, 2004.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00390 INSP-Sprinkler Rough-in/Hydro12/10/200412/13/200412/13/2004 12:00:00 AMAPASS
Overhead hydro test passed 12/13/2004 12:36:18 PM
FIR04-00368 INSP-Conference12/10/200412/13/200412/13/2004 12:00:00 AMAPASS
Tenting for the sprinkler piping in the clubhouse/pool area is ok to cover. Still need cover inspection for the combustible concealed spaces that will be filled with insulation. 12/13/2004 11:47:23 AM
FIR04-00722 INSP-Sprinkler Rough-in/Hydro12/13/200412/13/200412/13/2004 12:00:00 AMAFAIL
Tenant space locked. Sprinkler contractor did not have access. To be rescheduled. 12/13/2004 9:24:06 AM
FIR04-00728 INSP-Final Inspection12/13/200412/13/200412/13/2004 12:00:00 AMPFAIL
There are two pendants off of a single 1" outlet in the storage room and the riser needs its annual inspection 12/13/2004 2:03:41 PM
BLD04-01963 FIRE-Final Inspection12/10/200412/13/200412/13/2004 12:00:00 AMPFAIL
New overhead door in existing storage room obstructs upright sprinkler heads, provide one more fire extinguisher near the storage room entrance, provide approved door hardware on the restrooms and remove thumbturns at the main exits 12/13/2004 4:21:47 PM