Inspections for the day of: Wednesday, December 13, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00135 FIR-Aging Inspection12/13/200612/13/200612/19/2006 12:57:11 PM DONE
wip
FIR06-00838 INSP-Sprinkler Rough-in12/13/200612/13/200612/14/2006 11:01:13 AMPFAIL
Incorrect and missing tenting at one location, the maximum bending deflection distance exceeds the allowable amount at one room on the east side, approved plans must remain on site at all times per condition of the permit.
FIR05-00738 INSP-Final Inspection12/12/200612/13/200612/14/2006 10:12:37 AMAFAIL
Missing automatic ball drip at the FDC, missing seismic bracing at the basement level 2.5" main as noted, escutcheons need to be installed at some locations.
FIR05-00537 INSP-Final Inspection12/11/200612/13/200612/14/2006 7:10:07 AMPCANC
Alex ; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett To be rescheduled per phone call from contractor.
BLD06-02302 FIRE-Final Inspection12/13/200612/13/200612/14/2006 7:09:05 AMPNR
Project not yet completed for life safety final inspection at this time.
FIR06-00725 INSP-Final Inspection12/13/200612/13/200612/14/2006 7:08:10 AMPPASS
Fire sprinkler permit finaled.
FIR06-00882 INSP-Final Inspection12/12/200612/13/200612/13/2006 1:22:20 PMAPASS
Inspection passed, fire alarm permit finaled.
FIR06-00769 INSP-Alarm Testing12/6/200612/13/200612/13/2006 1:21:24 PMAPASS
Fire alarm testing passed field inspection.
BLD05-00807 FIRE-Final Inspection12/12/200612/13/200612/13/2006 11:19:29 AMAFAIL
Wrong permit number called in for request, was intended for building 2901. Noted missing fire exitnguishers and three SD in the bedrooms at the 2nd floor unit which will require relocation due to proximity to HVAC diffusers.
BLD06-02813 FIRE-Final Inspection12/12/200612/13/200612/13/2006 10:58:42 AMAFAIL
Building modifications have disrupted existing fire sprinkler and alarm coverage at the remodeled area, as noted on fire code review notes an alarm and sprinkler permit will be required for modifications to the existing system for code compliance.
FIR06-00965 INSP-Final Inspection12/11/200612/13/200612/13/2006 10:24:51 AMAFAIL
Two upright heads are blocked by ductwork in the upstairs mezzanine, storage heights at some locations also create obstructions to discharge.
FIR06-00435 INSP-Final Inspection12/12/200612/13/200612/12/2006 3:09:50 PMAPASS
Fire sprinkler final inspection passed, permit finaled.