Inspections for the day of: Wednesday, December 13, 2006.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00515 INSP-Sprinkler Rough-in/Hydro12/12/200612/13/200612/13/2006 4:22:51 PMPPART
Dry system hydro test passed. The FDC hydro test failed.
FIR06-00752 INSP-Sprinkler Rough-in12/12/200612/13/200612/13/2006 4:21:42 PMAPASS
The rest of the sprinkler piping is ok to cover
FIR06-00750 INSP-Final Inspection12/12/200612/13/200612/13/2006 2:31:23 PMAFAIL
Shut down of the hvac units by the duct smoke detectors did not function. It appears it might be a controls problem.Need to verify signals, install the foam filters on the sample tubes and remove the plastic short sample tubes since the steel one have been provided. All other fire alarm items are ok.
BLD06-01554 FIRE-Final Inspection12/12/200612/13/200612/13/2006 2:29:18 PMAFAIL
Fire alarm permit needs finaling
FIR06-00722 INSP-Final Inspection12/13/200612/13/200612/13/2006 2:28:00 PMPPASS
Permit finaled
FIR06-00962 INSP-Final Inspection12/13/200612/13/200612/13/2006 1:14:48 PMPPASS
Permit finaled