Inspections for the day of: Thursday, December 13, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-04050 Electrical Rough-In12/13/200712/13/200712/13/2007 4:28:14 PMPPASS
This is for an underground inspection, please call Jon NOvack with any questions. Phone #: ###-#### x0000 Internet Inspection Request from: Sandee Johnson ok to cover u/g
ELE07-02297 DOC - Permit Finaled12/13/200712/13/200712/13/2007 2:50:07 PMPPASS
ok to final permit
ELE07-03176 Final12/13/200712/13/200712/13/2007 2:45:03 PMPPASS
looked at signs, ok to final
ELE07-04103 Rough-In Permanent Service12/13/200712/13/200712/13/2007 2:29:22 PMPCANC
mike Phone #: ###-#### wrong type request see p/s
ELE07-04103 Permanent Service12/13/200712/13/200712/13/2007 1:56:25 PMPPASS
mike Phone #: ###-#### need to see u/g house to garage, p/s u/g n ok
ELE07-04063 Rough-In Permanent Service12/13/200712/13/200712/13/2007 1:37:08 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Alan Lusk ric ok, p/s, u/g, n, ok
ELE07-03759 Electrical Rough-In12/13/200712/13/200712/13/2007 12:34:09 PMPPASS
Reinspection. Ceiling Phone #: ###-#### Internet Inspection Request from: Ryan Christensen corrections made, ok to cover ceiling
ELE07-03803 Electrical Rough-In12/12/200712/13/200712/13/2007 10:44:29 AMAPASS
late morning if possible. cell is ###-####. thanks Randy Phone #: ###-#### Internet Inspection Request from: Randy Fletcher met electrician, they are changing out water system from garage, ric addition ok
ELE07-04098 Electrical Rough-In12/11/200712/13/200712/13/2007 10:15:45 AMAPASS
james Phone #: ###-#### ric ok
ELE07-04098 Final12/13/200712/13/200712/13/2007 10:11:07 AMAPASS
james Phone #: ###-#### ok to final
ELE07-04102 Electrical Rough-In12/12/200712/13/200712/13/2007 10:09:23 AMAPASS
brian Note: if any question call him Phone #: ###-#### called contractor, left survey, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, ric rear structure ok to cover, Note: this structure must be attached to adjacent structure for branch circuits as installed to be ok
ELE07-03759 Electrical Rough-In12/12/200712/13/200712/13/2007 9:34:23 AMAFAIL
inspection for ceiling cover Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called contractor, left correction notice, nec 300.11(A) raceways shall be securely fastened in place, support wires shall be secured at both ends, no cables or wiring shall be supported by grid or tiles, 348.30(A) fmc shall be supported within 12" of termination point
ELE07-00573 Final12/12/200712/13/200712/13/2007 9:05:20 AMAPASS
Scheduled by a contractor via Hello! on 12/12/2007 at 2:47:56 PM. Contact: ###-####. x-ray machine ok per 324, ok to final, signed occupancy card
ELE07-03754 Electrical Rough-In12/12/200712/13/200712/13/2007 8:33:33 AMAPART
Scheduled by a contractor via Hello! on 12/12/2007 at 10:22:36 PM. Contact: ###-####. met contractor, left correction notice for open ceiling in electrical room-nec 110.26(F)(1)(a)&(b) the space equal to the width and depth of the equipment to a height of 6' above the equipment shall be dedicated to the electrical installation. Shall install drip protection for foreign systems above dedicated space, ok to cover walls and hard lid ceilings